Appendix A - Wire Selection Tables
General Instructions For Electrical Wiring
1. Refer to Table 13 to determine the required wire gauge for general wiring,
such as relay wiring. Calculate the permitted voltage fall with respect to
loads current, wire gauge and length of wires.
2. Refer to Table 14 to select wire gauge for power supply wires. DO NOT
connect any circuit or load to detectors’ supply inputs.
Table 13: Maximum DC resistance at 68 F for copper wire
AWG # mm
2
Ohm per 100 ft.
Ohm/100
meter
26
0.12 - 0.15
4.32
14.15
24
0.16 - 0.24
3.42
11.22
22
0.30 - 0.38
1.71
5.60
20
0.51 - 0.61
1.07
3.50
18
0.81 - 0.96
0.67
2.20
16
1.22 - 1.43
0.43
1.40
14
1.94 - 2.28
0.27
0.88
12
3.09 - 3.40
0.17
0.55
10
4.56 - 6.64
0.11
0.35
A. Select "Number of detectors" connected in one circuit.
B. Select "wiring length" per your installation requirements.
C. Refer to "power supply range" for voltage extreme applied.
Table 14. Wiring length in feet (meter)
No. of
Detectors
Recommended Wire Diameter
(AWG)
Power Supply
Range (VDC)
24
18
16
14
-
-
22-32
20
18
16
14
-
-
22-32
16
20
18
16
14
-
22-32
12
20
18
16
14
-
20-32
8
20
18
16
14
-
20-32
4 and less
20
18
16
16
14
20-32
Feet
164
328
492
656
820
(meter)
(50)
(100)
(150)
(200)
(250)
Max. Length from Power Supply to Last
Detector
Summary of Contents for SharpEye 20/20R
Page 2: ......
Page 4: ......
Page 8: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 IV ...
Page 46: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 38 ...
Page 48: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 40 ...
Page 54: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 46 ...