4.3.1 Function switch (SW1):
The user can select the desired mode of operation by means of this switch
according to table 5:
Table 5: Function Switch SW1
SW.
ON Position
OFF Position
1
Alarm latching - enabled
Alarm latching – disabled
(default)
2
Accessory relay activated at warning
level
Accessory relay activated at
detection level (together with Alarm
relay) -
(default)
3
Automatic & manual BIT
(default)
Manual BIT only
4
Successful manual BIT activates the
Alarm relay and the 4-20mA output
turns to 15mA for approximately 3
seconds
(default)
Successful manual BIT does not
activate the Alarm relay.
5
Successful manual BIT activates the
accessory relay and the 4-20mA
output turns to 10mA for
approximately 3 seconds
(default)
Successful manual BIT does not
activate the Accessory relay.
6*
Sensitivity range – see table 6 below
(default)
Sensitivity range - see table 6
7*
Sensitivity range - see table 6 below
Sensitivity range - see table 6
(default)
8
Accessory relay used as End Of
Line.
Accessory relay operates in
accordance with the settings of
SW1
(default)
* See Table 6 for sensitivity range setting.
Table 6: Sensitivity range
Sensitivity
Range
SW1-7
SW1-6
1 (lowest)
16.5 ft (5m)
OFF
OFF
2 (highest)
50 ft (15m)
OFF
ON
Summary of Contents for SharpEye 20/20R
Page 2: ......
Page 4: ......
Page 8: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 IV ...
Page 46: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 38 ...
Page 48: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 40 ...
Page 54: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 46 ...