Spectrex Inc. - SharpEye
TM
Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005
16
D. Automatic & Manual BIT (SW1-3 = ON)
Manual Bit
Functions as described in Para. 4.4.c. In the case of an unsuccessful BIT all
outputs will function as described in para. 4.4.c, but the BIT will be automatically
executed every 1-minute. This mode of operation will continue until two
consecutive successful BIT's have been encountered. As a result, the detector will
resume its normal operation.
Automatic BIT
The detector automatically performs a BIT every 15 minutes.
A successful BIT sequence does not activate any indication:
•
The FAULT relay
is CLOSED (NORMAL).
•
The POWER LED
is ON (NORMAL).
An unsuccessful BIT sequence activates the following:
•
The FAULT relay
is opened.
•
4-20mA output
indicates FAULT (0mA).
•
The POWER LED (yellow)
flashes (4 Hz).
•
BIT procedure
will be performed every 1 minute.
Summary of Contents for SharpEye 20/20R
Page 2: ......
Page 4: ......
Page 8: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 IV ...
Page 46: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 38 ...
Page 48: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 40 ...
Page 54: ...Spectrex Inc SharpEyeTM Single IR Flame Detector Manual TM 20 20R Rev A January2005 46 ...