Troubleshooting
TM888300 Rev. (Al), August 2019
59
9
Troubleshooting
Table 14: Troubleshooting
Problem
Cause
Solution
“Maintenance call”
Status OMN: Signals are
below 2.5VDC at Gain 4
Status RMN: Ratios are
below 0.5
Poor alignment
Perform alignment
Dirt on the window
Clean the window
Poor light source
Replace the light source
Detector fault
Replace/repair detector
NQR at below the
permitted limit
Gas in the path
Make sure that the path is
clean and that the weather
conditions are good
NQR at above the
permitted limit
Poor alignment
Perform alignment
Temperature higher than
77°F/25°C beyond the
room temperature
Electronic problem
Replace/repair detector
Ratio1 and Ratio2 out of
the limit
Poor alignment
Perform alignment
Dirt on the window
Clean the window
Detector fault
Replace/repair detector
Voltage less than 16VDC.
The Detector at “V” fault
.
Low input voltage
Check the power supply
and installation