Series 200 IR Gas Detector - User’s and Maintenance Manual
Doc. No. TM792100, Rev. B, Oct..1997
- 28 -
2. 4. 3.
Installation Surface Preparation (Figure 2-2)
The following instructions are applicable for both the Flash Source unit and the
Detector unit.
1. Check the Air Duct Installation Surface (1) stability. It should be as near as possible
to a rigid girder connection in order to assure proper support to the mounting and
the unit. Also the surface must be stable and free of vibrations.
2. Locate the best installation surface for the Detector/ Flash Source. The location of
the central point of each Duct Hole (3) should be at the same distance from the
surface edge. This will provide that both Detector and Source optical axis will be in
parallel to the Air Duct wall lines such that any blocking in the interior area will be
prevented.
3. Preparation of the surface: Prior to holes drilling it should be verified that the
Installation Surface is straight, clean and free of corrosion.
Drilling and cutting: Mark the Location and dimensions of the Installation Surface
according to the drilling dimensions given at Figure 2-2. Drill the Duct Hole (3) and
the Screw Holes (2) carefully.
Caution!
Since the installation is done in an explosive environment, any
workmanship in the installation area should be performed
under the appropriate rules and regulations.
LEGEND:
1. Air Duct Installation Surface
2. Duct Mount Screw Securing Hole
3. Hole for Detector / Flash Source
Figure 2-2. Drilling Layout Dimensions for Duct Installation