SpectraPure
®
SpectraPure
®
Inc.
480.894.5437 Call us toll-free 1.800.685.2783
2167 East Fifth St, Tempe, Arizona 85281
16
TROUBLE SHOOTING GUIDE
Problem
Cause
Corrective Action
Low production rate.
a. plugged prefilters.
i. Replace prefilters.
b. low water temperature.
ii. Use higher GPD membrane.
c. fouled membrane.
iii. Replace membrane.
d. plugged flow restrictor.
iv. Replace flow restrictor & membrane.
Zero production rate.
a. Dried membrane.
i. Replace membrane.
b. Power supply not plugged in
ii. Plug power in.
c. Both floats need to be dry
iii. Both floats need to be dry and level, not drooping
Extremely high production rate.
a. Ruptured membrane.
i. Replace it.
Milky colored water.
a. Air in system.
i. Air in the system is a normal occurrence with initial
startup of the RO/DI system. This milky appearance
will disappear during normal use within 1-2 weeks.
The water in the Pure Water container drains out when not used.
a. The system is not elevated higher
than the Pure Water container
i. Elevate the system higher than the Pure Water
container to avoid siphoning.
Cannot adjust waste water flow
a. W.F. adjustment valve in lock
position
i. Unscrew lock nut on W.F. valve
REPLACEMENT AND OPTIONAL PARTS
Part No.
Description
SF-ZZ-0.2-ABS-20
0.2 micron ZetaZorb
®
Sediment Filter (1st Stage)
CF-0.5-20
0.5 micron Carbon Block Prefilter (2nd Stage)
MEM-LAB-0400
Replacement Membrane (3rd Stage)
DI-MC-20
20 in. MaxCap
®
Deionization Cartridge (4th Stage)
DI-SB-20
20 in. SilicaBuster™ Deionization Cartridge (5th Stage)
V-SOL-4-PL-DEMA
1/4 in. Solenoid Valve
PSP-400UHE-PUMP-230
High-Volume Upgrade Commercial Pump