Revised Date: 2017/08/24 

Installation 
 

Mounting on electric box 

 

1.  Separate back plate from the controller by loosing the cover screw; 

2.  Align the mounting holes on the screw holes of the electric box(applicable to 65x65 or US standard box); 

3.  Fix the back plate on the electric box by tightening the back plate screws. Suggest to use Philips wider “truss head” or 

“washer head” #6-32x 3/4”(20mm).  

4.  DO NOT let the bolt head rise above the wall of mounting holes of back plate. It might cause the short circuit of the 

controller. 

 
Mounting front cover 

 

1.  Lock front cover on the back plate by tightening the cover screw underneath with screw driver of Philip electronic 

instrument type or similar. 

 

Wiring Example 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1.

 

All wires come from electric box must be inserted above the retainers of respective terminal block before 
tightening the captive screws; 

 

   

I/O 

AO1(0~10VDC) 

DO1(SPDT Relay) 

RS 

ESI 

Modulating Type 
Heating Output 

On/ Off Type Heating 
Output 

Remote Temperature 
Sensor(NTC 10K) 

Occupancy Contact 

 

 
 

Summary of Contents for TE221 Series

Page 1: ...cons Displaying set point temperature while it is flashing 8 AUTO icons Device is in Using 9 Flake icon NA 10 Hot spring icon Indicate working on Heating mode 11 Flow icon NA 12 Gear icon Indicate Hea...

Page 2: ...NOT let the bolt head rise above the wall of mounting holes of back plate It might cause the short circuit of the controller Mounting front cover 1 Lock front cover on the back plate by tightening the...

Page 3: ...s no button pressed for 10 seconds Item Description Remarks 1 Normal Display Display Current Room or Set Point Temperature and Current Time Day Setting SP Parameter in Engineer Table to Choose Curren...

Page 4: ...Revised Date 2017 08 24 4 Fig 2 User Mode operation sequence...

Page 5: ...Revised Date 2017 08 24 5 Overview for the settings of Clock and Schedules Press or POWER button to escape any time during setting...

Page 6: ...Revised Date 2017 08 24 6 1 Detailed State Diagram for Clock Setting...

Page 7: ...for Schedule Setting Press Mode button to select day shows steadily deselect day flash Press MODE button to toggle Cooling Heating Set points Press MODE button to toggle Cooling Heating Set points Pre...

Page 8: ...Sch 2 8 00 16 0 8 00 16 0 8 00 16 0 8 00 16 0 8 00 16 0 8 00 16 0 8 00 16 0 Sch 3 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 Sch 4 22 00 16 0 22 00 16 0 22 00 16 0 2...

Page 9: ...c and maximum adjustment AO1 High E6 from 8 to 10 Vdc These two output voltages can be gauged by multimeter during setting to reflect the setting change effects 2 Reverse Output The output voltage can...

Page 10: ...ng Heating to be ESIC ESIH refer to Engineer table for details When the contact is deactivated Room back to be occupied it will set the set point values back as normal 2 If disable local ESI contact d...

Page 11: ...Revised Date 2017 08 24 11 c STOP mode means stop to use manual S P until manually activate schedule again And the icon will be NOT shown on the LCD...

Page 12: ...ress UP or DOWN button to change the setting and press MODE button to confirm the setting and return to menu item selection For no button pressed for 10 seconds it will go back to menu item selection...

Page 13: ...ot Used E9 SP L Low Limit for Temperature Set Point 10 0 0 50 0 50 0 32 0 122 0 1 0 C F E10 SP H High Limit for Temperature Set Point 35 0 0 50 0 95 0 32 0 122 0 1 0 C F E11 OFSt Current Temperature O...

Page 14: ...lt in 1 remote E16 SP Display Present Value of Temperature or Set Point for Normal Displaying 0 0 1 0 0 1 0 display PV 1 display SP E17 rE C Not Used E18 rE H Modulating Heating direct reverse signal...