background image

10

L100001

 

11

CLEARANCES

CLEARANCES TO COMBUSTIBLES 

MANTEL CLEARANCES 

NOTE: The combustible area above the facing must not protrude more than 

3

/

4

" from the facing. If it does, it is 

considered a mantel and must meet the mantel requirements listed in this manual. 

Follow these instructions carefully to ensure safe installation. Failure to follow instructions 
exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other 
than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed 
on a metal, wood or noncombustible material panel extending full width and depth of 
the appliance.

WARNING

The fireplace face m

ay

 be

covered with

 any non-

combustible ma

terial.

Allow clearance for

 removal

of front air panel

 and glass door.

6

6

6

6

6

6

6

6

14" min

48

" min

Minimum 7"
from both 
side walls

12" 

maximum

depth

COMBUSTIBLE MANTEL

to ceiling

Clearance to 

Combustibles

0.75     1      1.25    1.5    1.75    2       2.25   2.5     

2.5    

2.25      

2.0

1.75    

1.5    

1.25       

1.0   

0.75

*Minimum

 

7

 inches from Side Wall to Fireplace opening

Figure 6 - 

 

Side Clearance Chart

 (

1

5

9

  mm)

 Top                   

6.25

"

 To top standoff    

 

 0"     

  

 (0 mm)

Sides

  

 

 

1

"

    

  

 (

26 mm)

To side standoffs 

  

0"     

  

(0 mm)

B

 

a

 

c

 

k

1

.

 

5

 

"

 

 

(38 mm)

To back standoffs 

 

0" 

 

 

 (0 mm)

 

Floor

  

 

 

0"

    

 

 

 (0 mm)

Front

  

 

 

36"

      

 (915 mm)

 

Summary of Contents for DV48N-E

Page 1: ...ne in your building Do not try to light any appliance phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire WARNING Improper installation adjustment alterati...

Page 2: ...the Roof Installation 22 Installation for Vertical Termination 23 Cathedral Ceiling Installation 24 Fireplace Installation 25 Check Gas Type 25 Installing Gas Piping to Fireplace Burner Checking Gas...

Page 3: ...d and sealed If this unit is not properly installed by a qualified service person with glass panel properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carb...

Page 4: ...ed that you burn your fireplace for at least ten 10 hours the first time you use it Place the fan switch in the OFF position during this time A manufactured home USA only or mobile home OEM installati...

Page 5: ...SA B149 1 in Canada Gas and Propane Installation Code NFPA54 in U S A or the Natural Fuel Gas Code ANSI Z223 1 of local codes with the National with local codes or in the absence The installation must...

Page 6: ...or shipping damage and immediately inform the distributor if any damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed p...

Page 7: ...material over the facing are 60 x 34 1 2 see Figure 2 3 The inner opening in covering material must be minimum 49 1 4 wide 14 1 4 tall and centered over the fireplace opening to allow for or glass doo...

Page 8: ...RMATION Figure 3 Fireplace Dimensions Right side view Front view Top view Flue collar Electric access both sides Gas line access both sides 28 34 25 23 25 48 75 13 75 59 25 34 25 28 7 125 7 125 8 5 22...

Page 9: ...t the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section found in this manual for allowable ven...

Page 10: ...4 screws to attach fireplace to framing The side brackets are adjustable from 1 2 to 5 8 to accommodate different thickness of material SECURING FIREPLACE TO FLOOR OR FRAMING Figure 5 Securing Firepla...

Page 11: ...l flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING The fireplace face may be covered with any non comb...

Page 12: ...stem Installation of any component part not manufactured or approved by Spark Modern Fires Installation other than permitted by these instructions FINISHING MATERIAL NOTE Any remote wiring i e remote...

Page 13: ...be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNING Horizontal sections of this vent sys...

Page 14: ...s firestops are required at each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exteri...

Page 15: ...n air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved driveway located on public property 7 2133...

Page 16: ...cal line to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the...

Page 17: ...desired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have three locking lug...

Page 18: ...re 15 5 Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and inse...

Page 19: ...dations less than 20 below siding outcrop the vent pipe must flush up with the sid ing It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length...

Page 20: ...lbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizonta...

Page 21: ...leaving a clearance of approximately 4 below snorkel See Figure 21 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealan...

Page 22: ...f 45 elbows offsets may be used within the vertical sections From 0 to a maximum of 8 2 5 m of vent pipe can be used between elbows See Figure 26 DV 48 Series fireplaces allow for offsets This applica...

Page 23: ...x101 2 267mm x 267mm inside dimensions as shown in Figure 12 page 17 using framing lumber the same size as the ceiling joist If the area above the ceiling is an insulated ceiling or a room nail fires...

Page 24: ...Ceiling Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Ca...

Page 25: ...l regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could...

Page 26: ...raps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure...

Page 27: ...ty FRONT BACK see page 5 BLOWER FAN LOCATION Outlet Pressure Tap Pilot Adjustment Inlet Pressure Tap lower right outside wall as shown on page 5 Velcro 2 T o ease installation a 30 flex line with manu...

Page 28: ...tion and Canadian Electrical Code CSA C22 1 WARNING Label all wires before disconnecting when servicing controls Wiring errors can cause improper and dangerous operation CAUTION This fireplace require...

Page 29: ...SS FRAME REMOVAL 1 Remove the front air panel 2 Remove the left and right side panels by lifting up and moving to the center Figure 36 Removing Glass Frame and tilting out the upper right corner Front...

Page 30: ...re 37 on the support brackets as shown on figure 38 2 Fill the tray with media supplied Do not place media on burner or block air flow between burner and tray see figure 39 Figure 37 One piece media t...

Page 31: ...the screen in place Using the nuts provided attach the screen firmly 31 WARNING A barrier safety screen designed to reduce the risk of burns from the hot viewing glass is provided with this appliance...

Page 32: ...abs in the panel with the slots in the face and slide downward Make sure the side panel is secured properly Repeat Steps 5 and 6 for the Left Side Panel STEP 7 Angle the Air Front Panel beneath the bo...

Page 33: ...supply to the DFC board please verify that the electrical connections illustrated parts list or mounted in adjacent wall Make sure that the remote receiver switch is in REMOTE middle position Initiali...

Page 34: ...Note the polarity of the batteries and insert into the battery bay as indicated on the battery covel 2 Place the 3 posilion slider switch in the REMOTE position 3 Insert the end of a paper clip into...

Page 35: ...gnite A single beep from the receiver will confirm the command Turning OFF the Appliance 1 Press the ON OFF button 011 the transmitter The A single beep from the receiver will confirm the command the...

Page 36: ...changes etc Manual Override If the receiver or transmitter batteries are low or de pleted the appliance can still be turned on manually 1 Move the receivers three position slider to the ON position Th...

Page 37: ...the heater is installed and periodically during normal operation In normal operation at full rate and after operat ing for about 15 to 30 minutes the flame should be yellow and up to 6 inches high Se...

Page 38: ...rasive mild cleaning solution Simply apply an adequate amount to the glass and wipe off with a damp cloth After all maintenance has been completed re install glass door MEDIA Replace or add media as r...

Page 39: ...3 4 9 Pipe Length 58DVA 09 3 4 12 Pipe Length 58DVA 12 3 4 24 Pipe Length 58DVA 24 3 4 36 Pipe Length 58DVA 36 3 4 48 Pipe Length 58DVA 48 4 4 8 1 2 Pipe Extension 58DVA 08A 4 4 16 Pipe Extension 58DV...

Page 40: ...40 ILLUSTRATED PARTS LISTS 16 17 19 20 CONTROL COMPARTMENT BURNER COMPARTMENT ACCESS AND MEDIA COMPONENTS 1 2 3 4 5 6 7 8 9 10 11 12 21 13 14 15 22...

Page 41: ...t CPI IPI MODE 120 Vac INPUT 7 Vdc STABILIZED SUPPLY OUTPUT MOTOR IPI CPI RECEIVER DC SUPPLY SPLIT FLOW ON OFF TH TPTH DFC SUPPLY DC SUPPLY GROUND 885 PROFLAME Orange Green Chassis connection Remote c...

Page 42: ...T SIDE PANEL NOT SHOWN 1 23 H200011 H200011 GTMFS WIRE HARNESS 1 24 H200012 H200012 DFC TO CPI WIRE HARNESS 1 25 H100140 H100140 7V 10mA DC ADAPTER 1 1 H200010 H200010 REMOTE CONTROL RECEIVER 1 4 F200...

Page 43: ...mbustion chamber Ensure that the glass is properly secure and latch Frequent pilot outage A Pilot flame may be too high or A Clean and adjust the pilot flame for maximum flame impingement The pilot an...

Page 44: ...NOTES...

Page 45: ...NOTES...

Page 46: ...NOTES...

Page 47: ...uantity 45 Elbows ALTITUDE Feet Above Sea Level Was Stove Derated Yes No If Yes To What Orifice Size Unusual Structure Near Vent Inside Corner Trees Shrubs Other Termination Please Describe Prevalent...

Page 48: ...with the appliance and does not extend to 1 firebox burner assembly damaged by accident neglet misuse abuse alterations negligence of others inclu ding the installation thereof by unqualified installe...

Reviews: