26
L100001
27
��
�����
��
FIREPLACE INSTALLATION
A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged
1
/
8
" NPT pressure tapping
point should be installed upstream of the appliance.
See Figure 33.
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for
turning on or shutting off the gas to the fireplace.
Check your building codes for any special requirements for locat-
ing equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent
excess sealant from going into pipe. Excess sealant in pipe could
result in clogged burner system valves.
We recommend that you install a sediment trap/drip leg in supply
line as shown in
Figure 33
. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between
fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps
moisture and contaminants. This keeps them from going into the burner system gas controls. If sediment trap/drip leg is not
installed or is installed wrong, burner system may not run properly.
Figure 33 - Gas Connection
Tee Joint
Pipe Nipple
Cap
Approved Flexible Gas
Line
CSA Design-Certified Equipment Shutoff Valve
with
1
/
8
" NPT Tap*
Sediment Trap/Drip Leg
Natural Gas
From Gas Meter
(5" W.C. to 10.5" W.C. Pressure)
Propane/LP
From External Regulator
(11" W.C. to 13" W.C. Pressure)
NOTE : The gas line connection may be made using
1
/
2
" rigid tubing or an approved flex connector. Since some
municipalities have additional local codes it is always best to consult your local authorities and the current edition
of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CAN/CGA-B149 (1 or 2) Installation Code.
Only persons licensed to work with gas piping
may make the necessary gas connections to
this appliance.
WARNING
A manual shutoff valve must be installed upstream
of the appliance. Union tee and plugged
1
/
8
"
NPT pressure tapping point should be installed
upstream of the appliance.
See Figure 33.
CAUTION
Use pipe joint sealant that is resistant to liquid
petroleum (LP) gas.
CAUTION