![SpacePak WCSP-2430D Installation, Operation & Maintenance Manual Download Page 12](http://html1.mh-extra.com/html/spacepak/wcsp-2430d/wcsp-2430d_installation-operation-and-maintenance-manual_1339085012.webp)
12
Refer to Fig. 2.2 & 2.3 for condensate drain location.
Components for the PVC condensate trap are
provided in a separate bag with fan coil unit (see Fig.
2.12) and should be cemented together with PVC pipe
cement.
Do not use substitute trap. Do not cut
off or alter trap components.
Screw male adapter (see Fig. 2.12) into unit condensate
line connection. Assemble and cement remaining
components together. Then cement assembly to male
adapter. The 45° elbow provides an offset from beneath
the unit supply and return water piping to provide access
to the clean-out plug.
STEP 5: INSTALLING THE CONDENSATE TRAP & LINE
NOTE: PIPE SECTIONS ARE FIELD SUPPLIED.
SEE NOTE
˚
FIGURE 2.12: CONDENSATE TRAP ASSEMBLY
STEP 6: WIRING THE UNIT
Turn off electrical power supply before
servicing. Contact with live electric components can
cause shock or death.
All electrical and control wiring must be installed in
accordance with the codes listed in Section 1 of this man-
ual. Wiring diagram is provided in Figure 2.13. A
separate 208/230/60/1 power supply is recommended for
the unit. Use standard 15-amp fuse and 14-gauge wire
from power supply to unit.
Connect power supply to Terminals L1 (hot) and L2 (hot)
on the high voltage terminal block. Connect a ground wire
to the equipment ground terminal located next to
the high voltage terminal block.
The low voltage transformer in the unit has a 208 volt
tap in the primary winding (color coded RED). If unit is
to be operated with 208 volt electrical service, remove
the 230 volt ORANGE lead from the L2 terminal and
connect the 208 volt RED lead to the L2 terminal. Be sure
to insulate the end of the unused ORANGE lead.
Locate the room thermostat on a wall near the return
air box, approximately 60" from the floor. Connect the
low-voltage thermostat wiring from the room thermostat
to the low voltage control block in the unit.
Run a condensate line from the trap to a suitable
drain that’s in accordance with local codes. Make sure
the line is pitched
1
⁄
4
" per foot.
NOTICE: Never connect condensate line to a closed
drain system.