Form No. 43539470
Oct 2019 A
–7–
5.0)
SPECIFICATIONS
MODEL NO.
VF80CE (DSI)
INPUT RATING (kW)
Propane Gas:
73.3 max./46.9 min.
Natural Gas:
73.3 max./46.9 min.
GAS SUPPLY PRESSURE
Propane Gas:
Maximum
60 mbar
*Minimum
37 mbar
Natural Gas:
Maximum
60 mbar
*Minimum
20 mbar
MANIFOLD PRESSURE
Propane Gas:
24.9 mbar
Natural Gas:
10.0 mbar
ORIFICE SIZE
Propane Gas:
⌀
0.176” (4.47 mm)
Natural Gas:
⌀
0.290” (7.37 mm)
WEIGHT
50.8 kg
DELIVERED AIRFLOW
1,700 m
3
/h
VENTILATION REQUIRED
Per Heater
28.3 m
3/
per min
GAS CONSUMPTION
Propane Gas:
2.76 m
3
/hr - 10.33 liters per hr
Natural Gas:
7.0 m
3
/hr
GAS CONNECTION
Rp-1/2
ELECTRICAL SUPPLY
230 Vac, 1 Phase, 50Hz
TOTAL AMP DRAW
2.0A
MOTOR RATING
1/4HP, 1100 rpm
* The minimum inlet gas supply pressure for the purpose of input adjustment.
MODEL IDENTIFICATION:
Complete Model No.
Gas Type
Description
VF80CE-N5 DSI
Natural
Direct Spark Ignition NG – 73.3 kW
VF80CE-L5 DSI
Propane
Direct Spark Ignition LP – 73.3 kW
Module Electrical Rating:
Direct Spark Ignition DSI
Input-Control: 18-30 VAC
50/60 Hz (class 2
transformer)
Input Power-Line: 230 VAC
(L1, IND contacts only)
Flame Sensitivity: >0.7μA
minimum
3 ignition trials
3 second pre-purge period
10 second trial for ignition period
20 second inter-purge period