background image

 

 
The FB code is the stop time of the common fan and burners before any burner ignition. We  
 
Factory set this at 8 but can be adjusted to anything between 2 and 250 seconds. To set this 

Scroll through the parameters until you come to FB then Press 

, using 

scroll  

 
to the desired setting, we factory set this to 8 if a common fan is used. 
 
The FBF code is the stop time of common fan and burners after any burner ignition. We  
 
Factory set the at 8 but can be adjusted to anything between 2 and 250 seconds. To set this 

Scroll through the parameters until you come to FBF then Press 

, using 

scroll  

 
to the desired setting, we factory set this to 8 if a common fan is used. 
 
Once you have set both the FB and FBF settings reset the unit by pressing and holding the 

power button 

 until OFF is displayed then press the power button 

 to turn the unit  

 
back on. 
 
 

See section 4.2 on page 2 and 3 as well as Section 17 on page 6 in the manual for 
more help. 
 
 
 
5. FN is to Enable the Zones, Automatically, Manually or via Time settings as well as 

Enable the Burners. 

 

Press 

 (SET will be displayed) then , 

 then, 

 then, 

 this will display FNC. 

Press 

 this will display AN-1, this is  

 

ZONE 1, (if there is more than one they will be AN-2, AN-3 or AN-4) if then press 

 this 

will give you the first option which will be ON, if you press 

 you can change this to Auto 

or OFF. Press 

 once you have set the zone. See Section 11.2 on page 4 of the manual. 

 
 
 
Once you have the Zones set to Manual. Auto Or Off. If you continue to scroll through the 

menu options from AN-1 by pressing 

 then 

 again En-1 will display. This is your 

Burner Enable options. Press 

 then the 

 key you can enable or disable the burner.  

 
See section 11.3 on page 5. You can repeat this to set EN-1 to En-4. 
 
 
 
 
 
 