SECTION 7: INFORMATION FOR LP GAS FLOOR MODEL HEATERS ONLY  

Heaters used with LP gas must be installed in accordance with the 
latest edition of the National Fuel Gas Code NFPA54, Standard for the Storage and Handling of LP Gas -
 NFPA 58, all state and local codes or the authority having jurisdiction. See Section 7.1 “LP models only -
 Regulator and hose assembly instructions” on page 8 for specific LP connection information.  
RFPA10C Installation and Operation Instructions  

The heater must be connected to the tank or cylinder by a UL Listed hose assembly or hard 
piping. A 15 foot assembly of UL Listed hose is included with each heater from Space-Ray under Part No. 
30522020. A single stage LP gas regulator (operation range: 10150 PSIG inlet and 11.0" W.C. outlet) having 
a POL fitting with an excess flow valve is included with each hose assembly as Part No. 30524000 (LP 
Cylinder Kit).  

The hose assembly must be visually inspected prior to each use of the heater. If it is evident there is 
excessive abrasion or wear, or the hose is cut, it must be replaced prior to the heater being 
put into operation. The replacement hose must be a UL Listed hose assembly.  

The volume of a given quantity of liquid LP gas in a container is directly related to its temperature. As a 
result, the vaporization rate of a tank or cylinder will decrease as the temperature drops and 
as the percentage of liquid in the container becomes smaller. Table 5 on page 
7 shows the approximate vaporization rate of a 100 lb. cylinder.  

 

Table 5: Maximum Continuous Flow in BTU/Hr. At Various Temperatures (Degrees F)  

Lbs. of Propane in 
Cylinder  

20 

F  

40 

F  

60 

F  

70 

F  

100  

167,000  

214,000  

277,000  

300,000 

 80  

137,000  

180,000  

214,000  

236,000 

 60  

109,000  

140,000  

176,000  

197,000 

 40  

**  

105,000  

131,000  

141,000 

 30  

**  

**  

107,000  

118,000  

 

** Rate of vaporization drops below the heater input rate.  

WARNING: Due to the continuous length of time the heater might be in operation, a 100 
lb. LP gas cylinder may not be suf-
ficient in size. Manifolding several cylinders together is a practical way of increasing the time of operation of t
hese heaters. Operation of the heater with insufficient sized cylinders or when the liquid level 
becomes too low will result in poor heater performance and can cause sooting. Consult your 
LP gas dealer for proper sizing of container.  

Always turn the gas off at the tank or cylinder when the heater 
is not in use. When in operation, keep the heater a safe dis-
tance from the LP gas container and combustible materials as indicated on the 
heater and in the instructions. Fasten LP cylinders securely so they cannot be knocked over.  

 

Summary of Contents for RFPA10C

Page 1: ...iance DO NOT touch any electrical switch DO NOT use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier CALL the fire department Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance ins...

Page 2: ...in in force EXCLUSIVE REMEDY The sole and exclusive remedy under this warranty is the replacement of the defective parts or heaters as hereinabove specified THE MANUFACTURER DOES HEREBY EXPRESSLY EXCLUDE ANY AND ALL LIABILITY FOR INCIDENTAL AND CONSEQUENTIAL DAMAGES UNDER THIS OR ANY OTHER WARRANTY Without intending to limit the aforesaid exclusion THE MANUFACTURER DOES HEREBY EXCLUDE ANY LIABILIT...

Page 3: ... 10 SECTION 9 LIGHTING AND SHUTDOWN INSTRUCTIONS 10 SECTION 10 CLEANING AND ANNUAL MAINTENANCE 11 SECTION 11 REPLACING PARTS 12 SECTION 12 REPLACEMENT PARTS LIST RFPA10C 12 LIST OF FIGURES FIGURE 1 OPTIONAL REFLECTOR ASSEMBLY 5 FIGURE 2 REGULATOR AND HOSE ASSEMBLY 9 FIGURE 3 GAS CONTROL KNOB SETTING POSITION 11 FIGURE 4 REPLACEMENT PARTS 14 LIST OF TABLES TABLE 1 MODEL INPUT RATING 4 TABLE 2 MODEL...

Page 4: ...ied service person This heater is for INDOOR INSTALLATION ONLY While the products of combustion are expelled into the building national codes require ventilation in the building to dilute these products of combustion The ventilation may be provided by gravity or mechanical means Refer to Section 8 VENTILATION AND COMBUSTION AIR on page 10 of this manual for minimum requirements for ventilation and...

Page 5: ...utoff Manual Valve Baso 6C Standing Pilot Ignition 100 Safety Shutoff Manual Valve WhiteRodgers 9A Standing Pilot Ignition 100 Safety Shutoff Thermostatic Controlled Valve Robertshaw Table 2 Model Dimensions DIMENSIONS RFPA10C HEATER 18 Dia x 32 3 4 PACKAGED 18 1 2 x 18 1 2 x 34 SHIPPING WEIGHTS 55 LBS SECTION 3 ADDING OPTIONAL REFLECTOR A 180 reflector can be used where it is desirable to direct ...

Page 6: ...r head with lip over the expanded guard and reflector Hex Nut 1 2 13 Washer Upper Head Heat Exchanger Welded Base Assembly Reflector SECTION 4 MINIMUM CLEARANCES TO COMBUSTIBLES The heater shall be operated only on a NON COMBUSTIBLE level floor Minimum clearances to combustible walls and ceilings are listed below Table 3 RFPA10C Clearances to combustibles MODEL RFPA10C FRONT SIDES REAR TOP CLEARAN...

Page 7: ...de make sure the heater and all gas outlets are turned off before the main gas supply is turned on Turn the gas pressure on and check for leaks To check for leaks apply a solution of soap suds to all connections and joints or check by one of the methods listed in Appendix D of ANSI Z223 1 NFPA 54 latest edition Natural Fuel Gas Code DO NOT USE AN OPEN FLAME OF ANY KIND TO TEST FOR LEAKS SECTION 6 ...

Page 8: ... liquid LP gas in a container is directly related to its temperature As a result the vaporization rate of a tank or cylinder will decrease as the temperature drops and as the percentage of liquid in the container becomes smaller Table 5 on page 7 shows the approximate vaporization rate of a 100 lb cylinder Table 5 Maximum Continuous Flow in BTU Hr At Various Temperatures Degrees F Lbs of Propane i...

Page 9: ...he plastic cap from the end of the 3 8 flare fitting Connect the 3 8 flare swivel nut on the end of the regulator hose assembly to the 3 8 flare tube fitting on the burner assembly as shown in Figure 2 Regulator and hose assembly on page 9 Use two wrenches to tighten this connection screwing the swivel nut clockwise onto the supported 3 8 flare fitting 7 1 3 After all the connections are made they...

Page 10: ...d hose assembly 10 ft min 3 8 Flare swivel nut 3 8 Flare fitting x 1 2 NPT burner assembly POL fitting Regulator assembly To LP gas Cylinder or tank ON OFF TURN BY HAND ONLY FULL PUSH TO TURN OFF SLIGHT PUSH TO FROM PILOT POSITION NEVER USE TOOLS LIGHT ...

Page 11: ...Form 41357040 Rev Jan 2010 10 ...

Page 12: ...er cap burner ports may be cleaned with a wire brush 10 2 5 Removal of burner cap also makes mixing tube of burner accessible for cleaning with a round wire brush 10 2 6 After cleaning reassemble burner cap on burner base with the three 3 8 32 fillister head screws 10 2 7 Screw burner all the way down on burner fitting and install burner alignment brackets 10 3 If the emitter shows any accumulatio...

Page 13: ...MODELS 6 04380000 Main Burner Assembly complete RFPA10C ALL MODELS 7 41859000 Burner Cap RFPA10C ALL MODELS 8 41858000 Burner Base RFPA10C ALL MODELS 9 40584000 Burner Alignment Bracket Assembly RFPA10C ALL MODELS 10 04094010 Shutter Plate Fixed RFPA10C ALL MODELS 11 04783010 Base Assembly RFPA10C ALL MODELS 12 41806020 Label Mounting Plate RFPA10C ALL MODELS 13 41847000 Washer Burner Fitting RFPA...

Page 14: ...40 Instruction Manual Not Shown RFPA10C ALL MODELS 45 41848010 Control Arm Nat Baso RFPA10C N6 46 41848050 Control Arm LP Baso RFPA10C L6 47 41783010 Control Arm Nat White Rodgers RFPA10C N6C 48 41783030 Control Arm LP White Rodgers RFPA10C L6C 49 43138090 Control Arm Nat Robertshaw RFPA10C N9A 50 43138100 Control Arm LP Robertshaw RFPA10C L9A 51 41870050 Bulb Retainer RFPA10C 9A 52 02152010 Hex H...

Page 15: ... 39 LP Gas 17 18 21 19 20 22 29 30 27 28 33 34 17 18 21 19 20 25 22 43 49 50 51 52 Capillary Bulb from gas valve 1 2 3 5 4 58 59 60 12 13 14 11 SCREWS NUTS WASHERS ARE STANDARD HARDWARE ITEMS AND CAN BE PURCHASED AT ANY LOCAL HARDWARE STORE ALL ILLUSTRATIONS ARE INTENDED TO GIVE THE GENERAL IMPRESSION OF UNITS ONLY WE RESERVE THE RIGHT TO ALTER ANY SPECIFICATIONS WITHOUT NOTICE 53 54 7 9 56 8 10 6...

Reviews: