General Specifications
Insulation
Display
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Weight
Dimensions:
Safety:
Ingress Protection
Class 2, Double insulation.
LED
32°F to 104°F (0°C to 40°C)
5°F to 131°F (-15°C to 55°C)
Maximum, non-condensing: 85%
0-2000 meters
0.2 pounds (90.7grams)
5.5” x 1.7” x 1.1” (140mm x 43mm x 28)
UL: 61010 - 1:2012, 61010-2-030: 2012,
61010-2-033: 2014
EMC
:
EN61326-1:2013, EN61326-2-2:2013
IP42
3
International Safety Symbols
Potential danger. Indicates the user must refer to the manual for important
safety information.
Indicates hazardous voltages may be present
Equipment is protected by double or reinforced insulation.
Indicates the terminal(s) so marked must not be connected to a circuit where the
voltage with respect to earth ground exceeds the maximum safety rating of the
meter.
Indicates the terminal(s) so marked may be subjected to hazardous voltages.
MAX
600V
The measurement category (CAT) rating and voltage rating is determined by a
combination of the tester and the test probes. The combination rating is the
LOWEST rating of any individual component.
Brief Description
Typical Applications
Category
Rating
Single phase receptacles
and connected loads
Three phase circuits
and single phase
lighting circuits in
commercial buildings
III
switchgear and distribution panels
III
soruce
CAT II
CAT III
Safety Category Ratings
AWARNING:
Input Limits
Function
Maximum Input
Voltage AC or DC
from one or both test probes. Refer to Input Limits section of this manual for maximum