Buzzer and Red Light Warning
This unit is equipped with
The BlastOff
TM
Leak Detection System
.
If the red
light and buzzer are on, you may have a leak in one of the gas lines.
Note:
To reset alarm, turn power off and close the nitrogen tank valves. Turn the
power back on. If the unit goes into “Stand-By” mode and shows an orange
light, the generator is operating properly and you have a leak downstream.
Correct the leaks and resume operation. Contact your distributor or the mfg.
as necessary. This is a safety feature designed to provide a safer operating
environment and to prevent equipment damages or failure
the pipe lines, loose fittings, faulty connection, etc. These leaks are potential safety
hazards, they can cause the nitrogen to deplete quickly, and could cause your N
2
-
BLAST
®
Nitrogen Generator to run in excess (decreasing the life of the unit).
Once a leak has been detected, the BlastOff™ will sound the buzzer, and the red
light on the lower left side of the cabinet will illuminate. To reset the BlastOff™,
simply turn off the N
2
-BLAST
®
Nitrogen Generator, and turn it back on. The N
2
-
BLAST
®
Nitrogen Generator, can be ordered with the BlastOff™ System Factory
installed or the system can be retrofitted in the field. Some rewiring is required to
field install.
Never reset repeatedly; if the BlastOff™ goes off daily, there is a real potential
issue. Consult your installer for a solution. The label below and the Logo above
will be on your FPS if factory installed.
BlastOff
TM
– Leak Detection System Wiring:
The BlastOff
TM
can be wired to an external alarm if the customer desires. The
internal relay is set to trigger when there’s an alarm indication. The relay’s dry
contact is configured with 11-14 termination normally open, and 11-12 are
normally closed. BlastOff
TM
Assembly and customer dry contact relay is located in
the upper left hand portion of the
N
2
-BLAST
®
Nitrogen Generator’ cabinet’s
interior.
BlastOff
TM
– Air Bypass Option
The BlastOff™ - Air Bypass Option ensures that nitrogen is the only supervisory
gas entering the FPS. It safeguards your installation all while providing piece of
mind knowing the FPS is being filled with nitrogen vs any other gas. It will alarm if
the N
2
-BLAST
®
Generator is being bypassed by the air compressor. It safeguards
against a maintenance technician from inadvertently leaving the “air bypass” open
or the N
2
-BLAST
®
being powered in the off position. It will provide a visual alarm
when it is in alarm mode. See wiring diagram in
and installation instruction in