South-Tek Systems N2Blast FPS-1750 Manual Download Page 12

N

2

-BLAST

®

 Nitrogen Generator FPS-1750, FPS-3000, and FPS-6000   

           South-Tek Systems

      

 

Version:

 7 

Revision Date: 5/24/16    

                                                                                                            

Page 12 of 25 

4.

 

An 110VAC power connection should be installed per local code by a qualified 
electrician.  See  the  wiring  diagram  for  specifics.  Optionally  a  standard 
110VAC power cord can be installed on the system by a qualified electrician. 

 

Warning: Secure the N

2

-BLAST

®

 Nitrogen Generator to the wall at the top 

and bottom flanges.  Failure to do so could cause damage or bodily injury. 

4.4

 

INSTALLATION (FOR N

2

-BLAST

®

 NITROGEN GENERATOR) 

The  installation  layout  drawings  are  provided  with  your  system  in  the 
documentation  package  of  the  system.  For  electronic  copies,  please  contact  your 
local distributor. Review and make sure the setup installations are followed per the 
installation  layout  drawings.  Ensure  that  you  follow  the  correction  installation 
drawing per your system’s design. In some cases, a nitrogen bypass system for pre-
filling  is  required  in  the  installations  to  meet  NFPA  (National  Fire  Protection 
Association) code. 

If  your  system  requirements  are  more  complex,  please  consult  your  sales 
representative or equipment installer for more detailed installation instructions. 

1.

 

The N

2

-BLAST

®

 Nitrogen Generator is designed with ½” inlet/outlet 

connections.  Use Teflon tape or similar on fittings to prevent leakage. 

2.

 

Install the “Supply Line” coming from the air compressor to the N

2

-

BLAST

®

 Nitrogen Generator Air Inlet. 

3.

 

Connect the N

2

-BLAST

®

 Nitrogen Generator to the storage tank and then 

to the systems Air Maintenance Device(s). 

4.

 

Once  connections  are  made  and  the  air  compressor  has been started 
up,  slowly  open  the  System’s On/Off Valve. 

a.

 

Air will start rushing through the nitrogen generator 

b.

 

If there is a leak or bad connection, shut valve off, depressurize the 
line, and fix the issue. 

c.

 

If a  leak  within the unit, remove top cover and  locate  the issue. 
Only  use  factory  parts  supplied  from  your  distributor  or  South-
Tek Systems.  Consult the factory for any questions. 

5.

 

Once  the  N

2

-BLAST

®

 Nitrogen Generator

 

fills  the  nitrogen  storage  tank 

to  t h e   c u t - o u t   p r e s s u r e   ( ~ 80  PSIG),  the  system  will  enter  standby  -  
green light on the control panel will turn off and orange (standby) light 
will turn on. This  will  stop  the  air   flow through  the  generator   and  
eventually stop the air compressor once it reaches the cutout pressure. 

a.

 

This will save air and time on the compressor’s motor. 

b.

 

This also prolongs life of nitrogen generator’s media and filter life. 

i.

 

Lesser  quality  systems  have  a  constant  purge  flow 
through  their  systems  which decreases system life and 
increases the need for maintenance. 

6.

 

When  you  draw  nitrogen

 

from  the  system  and  the  tank  pressure  falls 

below  cut-in  pressure (approximately 72 PSIG), the pressure switch will 
trigger the system back into run mode and refill nitrogen into the  storage 
tank automatically. The pressure switch is preset at the factory – no field 

Summary of Contents for N2Blast FPS-1750

Page 1: ...FPS 1750 FPS 3000 FPS 6000 Fire Protection Systems O M Manual Version 7 05 24 2016 2020 The Leader in Nitrogen Generation Technology...

Page 2: ...Revision Date Approved By Approval Date Reason 1 J Nguyen 10 13 13 A Norman 10 13 13 Initial Release 2 J Nguyen 7 5 14 A Norman 7 5 14 3 J Nguyen 8 15 14 A Norman 8 15 14 4 J Nguyen 3 6 15 A Norman 3...

Page 3: ...ectrical Requirements 10 4 3 Mounting For N2 BLAST Nitrogen Generator 10 4 4 Installation For N2 BLAST Nitrogen Generator 12 4 5 Panel Layout and Gas Connection 13 4 6 Blastoff Air Bypass setup Option...

Page 4: ...N2 BLAST Nitrogen Generator FPS 1750 FPS 3000 and FPS 6000 South Tek Systems Version 7 Revision Date 5 24 16 Page 4 of 25 APPENDIX D INSTALLATION DIAGRAM 23 APPENDIX E APS INSTALLATION DIAGRAM 24...

Page 5: ...N2 BLAST Nitrogen Generator FPS 1750 FPS 3000 and FPS 6000 South Tek Systems Version 7 Revision Date 5 24 16 Page 5 of 25 Notes...

Page 6: ...Staff and should be read in its entirety prior to operation Please contact your local distributor provider for any operation and maintenance first prior to contacting the manufacturer 1 3 IMPORTANT IN...

Page 7: ...ator must follow safe working practices OSHA and local health safety code regulations during the installation operation and maintenance of the unit Warning This manual must be read in its entirety to...

Page 8: ...demand The generator comes with a built in pressure switch to indicate when the nitrogen demand is needed or has been met When the pressure switch is triggered nitrogen storage tank pressure is met it...

Page 9: ...gen Generator FPS 1750 FPS 3000 FPS 6000 Specifications Nitrogen Purity 98 0 Installation Wall Mounted Display Hours Operating Standby BlastOffTM N Storage Pressure Up to 80 PSIG Cabinet Port Connecti...

Page 10: ...80 F room o Always keep the N2 BLAST Nitrogen Generator in an upright position or in box as shipped o Do not connect the AC power cable until this manual has been read completely and all connections...

Page 11: ...6 2 Install the upper mounting bracket on a sturdy wall The brackets have a 16 center to center hole set for mounting to a standard studded wall a Use hardware min to support system weight Item 2 int...

Page 12: ...ply Line coming from the air compressor to the N2 BLAST Nitrogen Generator Air Inlet 3 Connect the N2 BLAST Nitrogen Generator to the storage tank and then to the systems Air Maintenance Device s 4 On...

Page 13: ...enerator is being bypassed by the air compressor It safeguards against a maintenance technician from inadvertently leaving the air bypass open or the N2 BLAST being powered in the off position It will...

Page 14: ...sure the amber Standby light will be illuminated Once the pressure drops to the cut in pressure the nitrogen generator will start replenishing the nitrogen into the storage tank The Operating green li...

Page 15: ...be ordered with the BlastOff System Factory installed or the system can be retrofitted in the field Some rewiring is required to field install Never reset repeatedly if the BlastOff goes off daily the...

Page 16: ...002 Prior to Filter Bowl Removal Ensure the power has been disconnected from the source Air supply to the unit should also be bypassed or disconnected from the unit You can remove the top cover to th...

Page 17: ...lement by twisting clockwise HAND TIGHT ONLY 4 Before reinstallation of the filter bowl rinse out the bowl of any debris with hot water and shake dry the water out 5 Change the O ring on the top of th...

Page 18: ...tions and your quickest solution on any issues you may have 8 FAQS 8 1 POWER ISSUES If the N2 BLAST Nitrogen Generator does not have power the production and storage of nitrogen will become apparent o...

Page 19: ...en Generator and the control panel has Blast Off light illuminated on the side panel of the unit If you hear the alarm and see the red BlastOff light on it means that the system is equipped with The B...

Page 20: ...manufactured or changed to a different specification at the factory s option Any work performed by an unauthorized person company or usage of non factory parts may void all warranties to the product A...

Page 21: ...om as possible on a horizontal section of piping or where water will not collect Ensure the Tees s 90 outlet is facing up so the main of the APS runs horizontally with the FPS piping Be sure that duri...

Page 22: ...N2 BLAST Nitrogen Generator FPS 1750 FPS 3000 and FPS 6000 South Tek Systems Version 7 Revision Date 5 24 16 Page 22 of 25 APPENDIX C WIRING DIAGRAM...

Page 23: ...N2 BLAST Nitrogen Generator FPS 1750 FPS 3000 and FPS 6000 South Tek Systems Version 7 Revision Date 5 24 16 Page 23 of 25 APPENDIX D INSTALLATION DIAGRAM...

Page 24: ...N2 BLAST Nitrogen Generator FPS 1750 FPS 3000 and FPS 6000 South Tek Systems Version 7 Revision Date 5 24 16 Page 24 of 25 APPENDIX E APS INSTALLATION DIAGRAM...

Page 25: ...N2 BLAST Nitrogen Generator FPS 1750 FPS 3000 and FPS 6000 South Tek Systems Version 7 Revision Date 5 24 16 Page 25 of 25 Last Page...

Reviews: