RELEASED TO PRODUCTION
RTD3
TC-/RTD2
+ -
RS485
+ -
AOI
24V
0V
TC+/RTD1
RTD3
TC+/RTD1
TC-/RTD2
AI2
AI3
V/MA -
AI4 / I7
AI5 / I6
I5
I4
I3
I2
I1
I0
FC0
NTC
C2
NO4
NO3
NO2
NO1
NO0
+
AOV
+12V
-12V
AOV
-
C1
AI0
AI1
T
P
COMMON ALARM DRY CONTACTS
R2
R2
11
11
14
12
*SEE NOTE 1 & 2
0VDC
+24VDC
0VDC
+24VDC
SOL-5
SOL-3
SOL-2
SOL-1
JUMPER WIRE
R1
A1
A2
SOL-4
TB-2
TB-3
TB-2
TB-2
TB-4
TB-6
TB-5
TB-5
TB-5
TB-6
TB-6
TB-6
TB-9
TB-8
PRESSURE SWITCH 70 PSI
MAGNETIC SWITCH
PRESSURE SWITCH 50 PSI
BUZZER
SSR-COIL 20A
PRESSURE DUMP VALVE
COOLING FAN
CCV/A
CCV/B
EQ1
EQ2
TB-1
TB-2
4-20MA OUTPUT: 1) TEMPERATURE 2) O2 PERCENT 3) PRESSURE TRANSDUCER
*SEE NOTE 3
A1
A2
R3
TB-4
TB-5
BUZZER RELAY COIL
TB-10
TB-3
NTC THERMOCOUPLE
TB-7
MAX O2 SENSOR OPTION
TB-7
A1
R2
A2
COMMON ALARM COIL
-
+
12
11
R3
TB-1
TB-4
N2 PRESS. TRANSDUCER OPTION
TB-7
TB-8
NOTES:
OPTIONAL COMMON ALARM CONNECTION FOR (BYPASS, BLASTOFF, LOW N2 PRESSURE,
(1)
FILTER, & POWER LOSS ALARMS) FOR FIRE PANEL OR SIMILAR MONITORING DEVICE.
IF AN ALARM IS ACTIVE: 11-14 WILL BE OPEN, 11-12 WILL BE CLOSED.
(2)
ANALOG OUTPUT IS USER CONFIGURABLE; SEE O&M MANUAL FOR DETAILS
(3)
WIRING TABLE
AWG
COLOR
SERVICE
FIELD/INTERNAL
16-18
BROWN
24 + VDC
INTERNAL
16-18
BLUE
0V
INTERNAL
16-22
RED/BLACK
MV SIGNAL
INTERNAL
16-22
WHITE
1-5V SIGNAL
INTERNAL
16-22
ANY
4-20 MA SIGNAL
FIELD
TORQUE SPECIFICATIONS
ITEM
MIN-MAX
FUSE BLOCK
0.8 Nm - 1.6 Nm
TERMINAL BLOCK
0.4 Nm - 0.6 Nm
GROUND BLOCK
0.4 Nm - 0.6 Nm
PLC
0.5 Nm MAX
POWER SUPPLY
0.67 Nm MAX
TERMINAL BLOCK
FUNCTION
1-3 JUMPED
+24VDC
4-7 JUMPED
0VDC
8
PLC/NO0
9
PLC/NO2
10
PLC/NO4
11
L1
12
L2
SCALE:
DATE:
APPROVED:
REVISION:
ES-FPS-00900-RS
01
PJS
1:1
DRAWN:
2 OF 2
B
NUMBER:
SIZE:
SHEET:
DATE:
06/18/19
PROJECT NAME:
ELECTRICAL SCHEMATICS
WEIGHT:
MATERIAL:
FINISH:
ELECTRICAL SCHEMATIC, RELIABLE
INTEGRATION
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF SOUTH-TEK SYSTEMS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION
OF SOUTH-TEK SYSTEMS IS PROHIBITED.
SDA
06/28/19
D
C
B
A
1
8
7
6
5
4
3
2
D
C
B
A
8
7
6
5
4
3
2
1
DRAWN
APPR.
DATE
DESCRIPTION
CHANGED LEAD LENGTHS OF CUSTOMER WIRE AND REMOVED
POWER AND ALARM PLUGS AND CAPS
CHANGED LEAD LENGTHS PER CUSTOMER CHANGE. RELEASE TO
PRODUCTION
NEW PLC, NEW DRAWING FORMAT
01
10404
-
-
RD-091
C0
RD-091
-
SHEET
TASK#
REV
00
REVISIONS: ONLY THE LATEST 3 REVISIONS WILL BE SHOWN. OLDER REVISIONS CONSOLIDATED AND FILED.
03/20/19
NTA
KLM
MRT
PJS
06/18/19
PJS
PJS
MRT
ANGLES
1/8
1/16
.005
.03
.2
1
.5
X/X>10'
X/X<10'
.XXX
.XX
.X
X.
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES