P
The Leader in Nitrogen Generation Technology
FPS-900-RS O&M Manual
Version: 3; 3/2020
Page 17 of 28
See MODBUS addressing table below:
Function
Data Type
Modbus
RTU
Address
Units/Status
Read/
Write
Running / Standby
BOOL
00012
0=Standby, 1=Running
R
Common Alarm
BOOL
00004
1=Good, 0=Alarm
R
BlastOff Alarm
BOOL
00015
0=Good, 1=Alarm
R
Bypass Alarm
BOOL
10005
1=Good, 0=Alarm
R
N2 Low Tank Pressure Alarm
BOOL
10004
1=Good, 0=Alarm
R
Filter Alarm
BOOL
00029
0=Good, 1=Alarm
R
Filter Reset Confirm
BOOL
00031
0=Good, 1=Alarm
R
Filter Hours
Register
40019
xxxxx.x / hours
R
(2) Analog output (
4-20 OUT
)
Another useful and optional feature of (FPS) Reliable System units an analog signal
output (4-20 mA) for current readings of different data points as follow:
(i)
Ambient temperature “
4-20 out
dEgr.F
”
(ii)
Oxygen content (percent) “
4-20 out
p.CEnt
”
(iii)
Oxygen content (ppm) “
4-20 out
trACE
”
(iv)
Supply Pressure “
4-20 out
prEss
”
To setup the analog out:
1) Hold the (Set Button
)
for 5 seconds Passcode Screen will pop up
2) Press the (Set Button) one time to activate data entry, Enter (6557) using the (Up
and Down buttons)
3) Press the (ENT Button) to confirm the entry.
It will bring (Hold Set) Screen,
press (NEXT) button to get to the analog output screen “
4-20 out
”,
Using the (up and down buttons) buttons to change type of sensor, to confirm press (Set button).
To exits menu press (Next button)
to get back to main screen “running or standby”.
Note: For analog output standard units (without advanced options) only will offer ambient
temperature signal, check appendix A.