Installer Setup -
Automated Demand Response
34
Cool Setpoint Offset
(setup step 52)
Heat Setpoint Offset
(setup step 53)
Specifies how much the current setpoints in effect prior to an
event will be altered during an event when the ADR ACTION is
set to OBSERVE SETPOINT OFFSETS. The heat setpoint can be
automatically lowered by -1 to -10 degrees while the cool setpoint
can be automatically raised by 1 to 10 degrees
DISPLAY INDICATIONS WHEN AN ADR EVENT IS HAPPENING
After setting your desired values for use during an ADR event,
the scrolling display will give a little information when an event is
pending or active. For instance, when an ADR event has been sent
to your thermostat, you might see ADR STARTS at 4:15 to notify you
of a pending event. Once active, you might see ADR STOPS at 5:30.
When an event is active, you can press any of COOLER, WARMER or
MODE buttons, followed by the WARMER to opt out of the event.