29
Installer Setup
Dry Contact Operation
(setup step 42 - 43)
Dry Contact Polarity (setup step 42)
Open (Normally Open) - The dry contact is open until the connected device
closes the circuit.
Closed (Normally Closed) - The dry contact is closed until the connected device
opens the circuit.
Dry Contact Use (setup step 43)
CONDENSATE PAN - If CONDENSATE is selected when the dry contact
is active, the thermostat will lockout the compressor terminal(s) and
“CONDENSATE PAN OVERFLOW” will appear on the display.
OCCUPIED - If OCCUPIED is selected, when the dry contact is active, the
thermostat will be forced into the programmed occupied mode / setpoints
and the ‘occupied’ icon will blink. This setting is useful for allowing a twist
timer to force occupied settings.
FDD - If FDD is selected when the dry contact is active, “EQUIPMENT
FAULT” will appear on the display.
HOLIDAY - If HOLIDAY is selected, when the dry contact is active, the
thermostat will be forced into the programmed unoccupied mode /
setpoints and the ‘unoccupied’ icon will blink.
Skyport
(setup step 44)
Set to ON to allow access to Skyport services or to OFF to not allow access to
Skyport services.
Local API
(setup step 45)
Set to ON to allow 3rd party software to interface with your thermostat such as
home automation software.
Fahrenheit or Celsius
(setup step 40)
This feature allows the thermostat to display temperature in Fahrenheit or
Celsius.
Press Fan To Clear All Messages
(setup step 54)
This feature allows the user to clear all current error messages from the
display.