Installer Setup -
Automated Demand Response
33
ADR
(setup step 46)
Controls whether you want the thermostat to possibly respond to
signals from the utility provider. Select ON to allow this and to have
steps 47-53 appear.
ADR Action
(setup step 47)
Allows the user to determine what action is taken when an ADR
event is received.
Observe Setpoint Offsets – will offset the heat and cool setpoints by
the amounts specified in setup steps 52 and 53
Observe Static Setpoints – will set the heat and cool setpoints to the
values specified in setup steps 50 and 51
Event Max Cool Setpoint
(setup step 48)
Event Min Heat Setpoint
(setup step 49)
Specifies the range of allowable setpoint adjustments to be enforced
when any ADR signal has been received from the utility. Since
you might be paying more for energy while an event is active, you
can impose tighter limits on setpoint ranges that are only enforced
during the event.
Static Cool Setpoint
(setup step 50)
Static Heat Setpoint
(setup step 51)
Specifies the setpoints that will come into use during an event when
the ADR ACTION is set to OBSERVE STATIC SETPOINTS