Installer Setup
26
Max Occ Dehum Overcool (Setup Step 37) - Specifies how many
degrees below the Cool setpoint the air conditioning will run to
satisfy a Cool to Dehumidify demand. (0˚ - 5˚)
Max Unocc Dehum Overcool (Setup Step 38) - Specifies how many
degrees below the Cool setpoint the air conditioning will run to
satisfy a Cool to Dehumidify demand. (0° - 20°)
Reheat Operation With Cool To Dehumidify (Setup Step 39) -
Specifies if electric strip heat is allowed to turn on during a Cool to
Dehumidify demand to help maintain desired room temperature.
This step is not available if Electric Heat is not present.
Humidity Polarity
(setup step 47)
Open (Normally Open) means no voltage is sent to the HUM output
when there is no demand for humidity.
Closed (Normally Closed) means voltage is sent to the HUM output
when there is no demand for humidity.
Dehumidify Polarity
(setup step 48)
Open (Normally Open) means no voltage is sent to the DEHUM
output when there is no demand to dehumidify.
Closed (Normally Closed) means voltage is sent to the DEHUM
output when there is no demand to dehumidify.
Dehumidify Only with Cooling
(setup step 49)
When set to ON, Dehumidify will only turn on with a 1st stage
cooling demand. When set to OFF, Dehumidify will turn on at any
time that the room humidity exceeds the dehumidification setpoint.