19
Installation
Low voltage max
. 12VAC/DC connection in
the left-hand terminal compartment!
Terminal: Connection
for:
S1
Sensor 1 collector 1
S2
Sensor 2 store 1
S3
Sensor 3 (optional)
S4
Sensor 4 store 2
S5
Sensor 5 collector 2
S6
Sensor 6 (AntiLegionella,
see
7.7)
+ Not
used
- Jumper
terminal
block-
Connection of sensor earths (S1-S6) via
terminal block sensor-
The polarity of the sensors is freely se-
lectable.
Mains voltages
230VAC 50-60Hz Connec-
tion in the right-hand terminal compartment!
Terminal: Connection
for:
R1
pump 1 L (speed control)
N
pump 1 N
L
Mains phase conductor L
N
Mains neutral conductor N
R2
store valve L
N
store valve N
R3
collector valve L
N
collector valve N
The PE protective conductor must be con-
nected to the PE metal terminal block!
Brief description:
∆
T R1 (6.7) switches the pump at relay R1.
∆
T R2 (6.8) switches the valve at relay R2.
Priority (6.15) switches the valve at relay R2.
Switching between the 2 collectors occurs
when a temperature difference of at least
20°C is present.
Relay R1: For speed control of standard pumps, minimum load 20VA
Caution
D.9
2 collector + 2 storage tanks + valve
Caution
Danger
Mains side
230VAC
Sensor side
max. 12V