DESCRIPTION °CALEON SMART
Technical Data
2-part, ABS plastic
75 mm x 95 mm x 19 mm
Glass front
Capacitive touch panel
Color display with 240x320 dots
2.8 inches (7 cm) diagonal
Intuitive user guidance
Deutsch
English
Español
Italiano
Français
Português
Electrical specifications:
Power Supply
12 - 24 VDC +/- 10%
power consumption
max. 2,5 W
Protection Class
IP20
Protection class / overvoltage category
III / II 0/III
Max. Cable Length
CAN
<3m, if the cable length is >=3m it is necessary to use a shielded twis-
ted pair bus cable and connect the shield on one side to the protective
conductor.
1-Wire Bus
Optional, without function
Permissible Ambient Conditions
during operation
0 °C - 50 °C, no moisture condensation permitted
for transport/storage
0 °C - 60 °C, no moisture condensation permitted
Measurement Range
Outside the measuring ranges there are larger deviations
Internal temperature sensor
0 °C - 60 °C
Ac/- 1 °C
Resolution 0,1 °C
Internal sensor for rel. humidity
0 % - 100 %
Ac/- 6 °C
Resolution 0,1 %
1-Wire temperature sensors
Optional, without func-
tion
After switching on or disconnecting from the mains, it takes up to 60 minutes until the temperature is displayed precisely.
Other Specifications
Installation Methods
Wall installation, with/without wall socket
Real Time Clock
RTC with 24 hour power reserve
Scope of Supply
l
°CALEON Room Controllers
l
2 screws 3,5 x 35 mm and 2 plugs 6 mm for wall installation.
l
2 single conductor connectors, CAN connector with connecting cables, terminating resistor CAN connector, ter-
minating resistor °CALEON, operating tool
l
°CALEON Smart installation guide
5