Manual Supercom 646 GPRS rev. 04-02-2011
30
The values contained in the fields « Identification number, Manufacturer ID, Version et Device
type » of the block Rsp_xx (Device Type) must be transferred to the respective field of the block
« Selection of Slaves »
7.4 Writing concept in the radio central
Cf. Annex B, for the detailed schema of the writing process.
Cf. chapter Password to define the position of the field « Password » in the block.
7.4.1 Configuration modification of the radio central
Fill in the frame « Structured write » SND_UD (master to slave)
Field
Frame bytes in hex (Note 1)
Coding
Comment
Start,
L
ength
68,Le Le,68
C
ontrol
73|53
Send user data to slave, SND_UD
A
ddress
FD
C
ontrol
I
nformation
51
Stuctured write telegram
Enter password
0C,FD 16,xx xx xx xx
A, 32 bits
0
0
0
0
Set new password
4C,FD 16,xx xx xx xx
A, 32 bits Note 2
0
0
1
0
Current date & time
04,6D,xx xx xx xx
F, 32 bits Notes 2 and 3
DateAndTime
0
0
0
0
Identification number
0C,79,xx xx xx xx
A, 32 bits Note 2
IdentificationNumber
0
0
0
0
K2 module GSM PIN code
8D 80 40,FF 18,Lp ch ch ch
ch ch ch ch ch
LVAR
§ empty = disabled, Notes 2 and 7
PinCode
2
0
0
0
K2 module call back number
8D 80 40,FF 1E,Ln ch ch ch
ch ch ch ch ch ch ch ch ch
ch ch ch ch
LVAR
§ empty = disabled, Note 2
PhoneNumber
2
0
0
0
Add entry to device list
0D,FF 16,Ld xx xx xx xx xx
xx xx xx xx xx xx xx xx xx
xx xx xx xx xx xx xx xx xx
xx xx xx xx xx xx xx xx xx
xx xx xx xx xx xx xx xx xx
xx
LVAR
§ Notes 2, 4 and 6
DeviceListEntry
0
0
0
0
Clear device list
0D,FF 17,08 FF FF FF
FF FF FF FF FF
LVAR
Notes 2 and 5
0
0
0
0
Reset battery use duration
03,FD 6C,00 00 00
B, 24 bits Note 10
OperatingTimeBattery
0
0
0
0
Parameter flags (Bits set)
01,FD E6 03,pp
D, 8 bits
Mentioned bits are setted. Note 8
StateOfParameterActivation
0
0
0
0
Parameter flags (Bits clear)
01,FD E6 06,pp
D, 8 bits
Mentioned bits are cleared. Note 9
StateOfParameterActivation
0
0
0
0
C
heck
S
um
cs
Stop
16
Symbols
Notes
1. For non hexadecimal or lower case digits see the detailled description in the Keys sheet.
2. The password must be entered before to change this value.
3. Use the standard time all the year regardless of the daylight-saving time (as the radio devices).
4. The 646 needs at least 50 ms per device to add them to the list, don't send frame during this period.
5. The 646 needs at least 7.5 s to do this operation, don't send frame during this period.
6. At the end of the current link, the 646 needs up to 3 minutes to update its internal data and it is unavailable.
7. At the end of the current link, the 646 needs about 6 s to reinitialize the modem and it is unavailable.
8. For example, to set the bit0 the value is 01h, to set both bit1 and bit3 the value is 0Ah.
9. For example, to clear the bit0 the value is 01h, to clear both bit1 and bit3 the value is 0Ah.
10. Other values than 0 are not allowed. The "Radio reading counter" is also reset.
<MbusRecord> XML attributes
P
ar
en
t t
ag
N
am
e
S
ub
U
ni
t
T
ar
iff
S
to
ra
ge
F
un
ct
io
n‡
S
ta
rt
‡ Function: 0=instantaneous, 1=maximum, 2=minimum, 3=during error state
U
se
r
D
at
a
E
nd
§ manufacturer specific VIFE
All the fields of the frame Rsp_2 which contain information about the configuration of the radio cen-
tral can be modified and inserted in the block « Structure write ».