S-36 VLF
– USER MANUAL
9
Other VLF standards. Requirements of the IEEE 400.2
TM
-2013
VLF test voltage for sinusoidal waveform:
Cable rating
Installation
Acceptance
Maintenance
phase to phase
phase to ground
phase to ground
phase to ground
RMS voltage
RMS or (peak voltage) RMS or (peak voltage) RMS or (peak voltage)
5 kV
9 (13) kV
10 (14) kV
7 (10) kV
8 kV
11 (16) kV
13 (18) kV
10 (14) kV
15 kV
19 (27) kV
21 (30) kV
16 (22) kV
20 kV
24 (34) kV
26 (37) kV
20 (28) kV
25 kV
29 (41) kV
32 (45) kV
24 (34) kV
28 kV
32 (45) kV
36 (51) kV
27 (38) kV
30 kV
34 (48) kV
38 (54) kV
29 (41) kV
35 kV
39 (55) kV
44 (62) kV
33 (47) kV
Conversion for other system voltages, which are not mentioned in this standard:
6.6 kV
10 (14) kV
11 (16) kV
9 (13) kV
11 kV
14 (20) kV
15.5 (22) kV
12 (16) kV
13.8 kV
17.5 (25) kV
19.5 (27.5) kV
15 (20) kV
22 kV
26.5 (37.5) kV
28.5 (40.5) kV
22 (31) kV
31.5 kV
35.5 (50.5) kV
40 (56.5) kV
30.5 (43) kV
33 kV
37 (52) kV
41.5 (58.5) kV
31 (44.5) kV
34.5 kV
38.5 (54) kV
43.5 (61) kV
32.5 (46.5) kV
Summary of Contents for S-36 VLF
Page 1: ......
Page 2: ......
Page 33: ...S 36 VLF USER MANUAL 31 NOTES...
Page 34: ...S 36 VLF USER MANUAL 32 NOTES...
Page 35: ......
Page 36: ......