4.6 Earth resistance measurement with two-clamp method (2C)
The two-clamp measurement is employed when there is no possibility of using auxiliary electrodes.
NOTE!
The two-clamp method is used specifically only in the case of multiple earth
ground systems.
Use the
<<
or
>>
buttons to select the
measurement mode:
. The LED
is
illuminated. The meter is now in the state of
measuring interfering noise voltage be-
tween the measurement terminals, and also
measuring current sensed by the receiving
current clamp.
Connect the transmission clamp to terminals
H
and
E
.
The measurement current clamp should be connected to the clamp terminal .
Attach the transmission clamp and the measurement clamp around the
tested earth electrode object of test at least 30 cm / 12 in from each other.
The meter is ready for
measurement.
Press
START
to begin measurement.
Connect the test leads according to this diagram: