background image

Scale:   

LSPo ... HSPo         

Factory set:    

4°C

10% -15% 50/60Hz max. 2VA

322

 - 2 relays max. 250V~12A. Potential free contacts

333 

- 3 relays max. 250V~, 2 (12A) + 1 (5A). Potential free contacts

344 

- 4 relays max. 250V~, 5A. Potential free contacts

Probe PTC2000 (-40°C to +140°C) / Probe PT1000 (-50°C to +200°C)

2

2

2

Section: Min. Power=0,75 mm  • Relays=1,5 mm  / Max.=2,5 mm
Temperature = 0 to 40°C / Humidity = 20 to 85% / Pollution = 2
Software classe A; Action Type1.B  According EN 60730
Impulse voltage of 2500 V
Ball Pressure Temp: 100°C (gripper parts voltage conductor)
                                      75°C (plastic parts accessible)

W

    

1323     1579     1865     2180    2525     2911     3326    3754

°C      -20          0         +20       +40       +60       +80      +100     +120

Power supply

Outputs

Inputs

Wiring H05v-k
Environment
Operation
Tests

Verification Scale

PTC2000

PT1000

W

      

921     1000     1078     1155    1232     1309     1385    1461

Energy control

105

90

26

22

10

58

14

14

45

62

 Technical Specifications

Operation

Reset of values

7496V1 ABR16

Statistics

EtMA 

EtMi 

EtAG 

EHor 

EHot 

- Probes Maximum Temperature 1, 2, 3, 4

- Probes Minimum Temperature 1, 2, 3, 4

- Probes Average Temperature 1, 2, 3, 4

- Partial Operating Hours 1, 2, 3, 4

- Total Operating Hours 1, 2, 3, 4

Keys            changes the value 
assigned and        confirmed.

Set  point  setting  for  the 
t h e r m o s t a t   f u n c t i o n  
currently displayed.

Measures  

mm - 

Rail-DIN installation

 Electrical Drawing

RAIL 344

ESC

OK

Sonder

RAIL 322

Manual Instructions for Installation & Use

Menu 

Deletes  all  adjustments  to 
parameters,  functions,  and 
statistics  (except  total  relay 
operating  hours),  sets  back  to 
factory default values. 
With  password  only  come  into 
test probes and relays. Leaving the 
test relays return to their original 
state.

 - Before setting values and parameters menu, it is advisable to perform the probe and relay test to verify the correct operation 

of the installation.

RAIL 322, 333

 & 

344

 are electronic thermostats with probes & relays freely assignable. You can assign a different probe for each 

relay & can working as functions of independent thermostats, or multiple relays to a single probe thus creating a neutral zone. 
Probes & relays that are not assigned to the functions are outside the operating device shall be operable only in manual mode.

- All parameters are factory set with default values, to fit into installation menu. Inside you can activate the functions of 

independent thermostats, choose the probes type to connect (PT1000/PTC2000), calibrate the probes, assign a password or 
set the type of lighting. To change the set point of the thermostat function displayed on the screen, press         for 2 seconds, 
with               change value and press        to confirm.

- Once all the connections and powered, the unit displays the screen in normal operating mode with the factory settings.

- If the electrical network failure control saves its settings in memory.

Examples of installations 

Function ter1:  t1+r1
Function ter2:  t2+r2

F. ter1:  t1+r1
F. ter2:  t1+r2
F. ter3:  t2+r3 can be used as alarm

1

OK

TEST

PRG

2

10 Vdc

(230Vac)

N

L

(230Vac)

C

NC

NO

(230Vac)

C

NC

NO

3

5s

t1

R1

R2

t2

R3

Function ter3:  t3+r3
Function ter4:  t4+r4

344 - 4 Independents thermostats

333 - thermostat with a NEUTRAL ZONE + Alarm

MAIN

WATER

MAIN

WATER

t1

A.C.S.

MAIN

WATER

MAIN

WATER

r3

1

OK

TEST

PRG

2

10 Vdc

(230Vac)

N

L

(230Vac)

C

NC

NO

(230Vac)

C

NC

NO

3

5s

r4

r2

r1

t3

t2

t4

A.C.S.

A.C.S.

A.C.S.

KWh

Display

ESC

OK

Sonder

4

3

1

2

2-

 Relay function enabled

3- 

Temperature probe

1- 

Relay assigned to tEr1

4-

 Thermostat Function 1

Programmation

Press           15 seconds

Press          5 seconds

Press both keys for 5 seconds

Press             2 seconds

Test   & Manual mode

Temperatures t1 a t4

Relays r1-r4 /r1-r3

Press           5 seconds

-  Connect  and  disconnect  the  relays 

manually to check the correct operation of 
your installation.

Press          to move onto the next probe.

- See current temperature of each probe, its 

assignation and operation performance. If 
this reading is erroneous you should check 
that  it  is  properly  connected  and  that  its 
cables are not severed. 

Pressing        switches relay 

R1 

on/off.

Pressing              move onto the next relay.

Sets  the  function  of  thermostats,  set  values,  define  what  type  of 
probes, calibrate probes, configure the type of display lighting and set 
a password.   

The Screen shows the SET icon

Very Important

- Press          to exit the manual mode when done since while inside, has 

disabled the regulation and its operation is limited to manual fixed 
orders.  Exiting 

TEST 

the  relays  update  your  status  to  the  system 

regulation.

- Totals and partials operating hours for relays.

-  Maximums,  minimums  &  averages  temperatures 

recorded by probes.

RAIL 333

RAIL 322 

Code: 26.205,

  

RAIL 333 

Code: 26.202,

  

RAIL 344

 

Code: 26.203

Electronic Thermostats

Password On: 

After 15 minutes without touching any key the systems exits into 

normal operation and the relays go back to the status required by 
the system at that moment.

Password OFF: 

Until the key 

            

is not pressed you have not exited test menu 

or forced manual mode.

- Pressing           sets the current screen

The display mode is configurable:

The display shows cyclically (8 seconds each screen) enabled thermostat functions, 
if all are off then shows the reading of the probes.

- Pressing           looks screens cyclically

C

L

5A

230V

~

N

Probe2

Probe1

Probe3

NO

r3

C

12A

NO

r1

C

12A

NO

r2

NC

NC

L

N

230V~

PT1000 / PTC2000

C

L

5A

230V

~

N

Probe2

Probe1

Probe3

NO

r1

L

N

230V~

PT1000 / PTC2000

Probe4

C

5A

NO

r2

C

5A

NO

r3

C

5A

NO

r4

L

230V

~

N

Probe2

Probe1

C

12A

NO

r1

C

12A

NO

r2

NC

NC

L

N

230V~

PT1000 / PTC2000

Goes to the next parameter saving changes
Change parameter value

Returns to the previous menu without saving changes

Setpoint F. thermostat

- The relays enabling your installation devices are potential-

free contact and work as switches only, which means that 
they only open/close contacts, & that they feed the devices 
connected to the relay corresponding to each device.

- Make sure to have properly made the electrical connections 

from the devices to the relay contacts before feeding the 
control.

- The probe cables should never be embedded in the same 

channel as the electrical wires.

-  It  is  recommended  to  use  original  probes  only,  If  need 

lengthen probes, the connection is to be done by welding 
to  keep  the  reading  and  shrink-wrapping  to  keep  isolate 
from moisture.

C-H

diFt

HSPo

LSPo

Sond

rELE

ICon

doFF

dit

dEt

 Independent Thermostat  1, 2, 3, 4

 Type of probe 1, 2, 3, 4

 Calibration probes 1, 2, 3, 4

 LiGT

 PASS

On

Off