Sha nghai Son

best Industrial Co., Ltd                                                                             Page3

 

        4 Read and Modify Baud Rate 
        (1) Read baud rate 

        The device default factory baud rate is 9600. If you need to change it, you can change it according to 
the following table and the corresponding communication protoco l. For example, read the current device's 

baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.  

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

  03 

00 67 

00 01 

35 D5 

        Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 
4 is 19200; 5 is 38400; 6 is 115200. 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 03 F8 45, the format of which is as shown in the following table: 

Device ID 

Function id 

Data Length 

Rate ID 

CRC16 

01 

  03 

02 

00 03 

F8 45 

        coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.  

        (2)Change the baud rate 

        For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the 

command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .  

Device ID 

Function id 

Start Address 

Target Baud Rate 

CRC16 

01 

03 

00 66 

00 01 

64 15 

        Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take 

effect immediately, at which point the device will lose its response and the baud rate of the device should 

be queried accordingly. Modified. 

        5 Read Correction Value 
        (1) Read Correction Value 

        When there is an error between the data and the reference standard, we can reduce the display error 

by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, t hat 

is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can 

correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If 
you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of 

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The 

correction value starts from 00 6B. We take the first parameter as an example. The correction valu e is read 

and modified in the same way for multiple parameters. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

03 

00 6B 

00 01 

F5 D6 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 64 B9 AF, the format of which is as shown in the following table: 

Device ID 

Function id 

Data Length 

Data value 

CRC16 

01 

  03 

02 

00 64 

B9 AF 

        In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the 

first state quantity correction value register. If the device has multiple parameters, other parameters 

operate in this way. The same, the general temperature, humidity have this parameter, the light generally 

does not have this item. 

        (2)Change correction value 

        For example, the current state quantity is too small, we want to add 1 to its true value, and the current 

Summary of Contents for SM2130B-H2

Page 1: ...9 24V 1A Dimensions 110mm 85mm 42mm Wiring instructions Any incorrect wiring can cause irreversible damage to the product Please carefully wire the cable as follows in the case of power failure and then connect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wi...

Page 2: ...FA is 250 for the general address When you don t know the address you can use 250 to get the real device address 00 64 is the device model register For the correct query command the device will respond for example the response data is 01 03 02 07 12 3A 79 the format of which is as shown in the following table Device ID Function id Start Address Model Code CRC16 01 03 02 55 3C 00 01 3A 79 Response ...

Page 3: ...queried accordingly Modified 5 Read Correction Value 1 Read Correction Value When there is an error between the data and the reference standard we can reduce the display error by adjusting the correction value The correction difference can be modified to be plus or minus 1000 t hat is the value range is 0 1000 or 64535 65535 For example when the display value is too small we can correct it by addi...

Page 4: ...ng any intellectual property rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes no warranties express or implied regarding the sale and use of this product including the suitability for the specific use of the product the marketability or the infringement liability for any patent copyright or other intellect...

Reviews: