01 

03 

00 00 

00 01 

84 0A 

        For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6 , the response 

format is parsed as follows:   

Device ID 

Function id 

Data Length 

数据

Check Code 

01 

03   

02 

00 79 

79 A6 

        Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is 

converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. 

Others and so on. 

        2. Data Address Table 

Address 

Start Address 

Description 

Data type 

Value range 

40001 

00 00 

1#hydrogenregister  Read only 

0~65535 

40101 

00 64 

model code 

read/write 

0~65535 

40102 

00 65 

total points 

read/write 

1~20 

40103 

00 66 

Device ID 

read/write 

1~249 

40104 

00 67 

baud rate 

read/write 

0~6 

40105 

00 68 

mode 

read/write 

1~4 

40106 

00 69 

protocol 

read/write 

1~10 

        3 read and modify device address 
        (1) Read or query device address 

        If you don't know the current device address and there is only one device on the bus, you can use the 
command FA 03 00 64 00 02 90 5F Query device address. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

FA 

03 

00 64 

00 02 

90 5F 

        FA is 250 for the general address. When you don't know the address, you can use 250 to get the real 

device address, 00 64 is the device model register. 
        For the correct query command, the device will respond, for example the response data is: 01 03 02 

07 12 3A 79, the format of which is as shown in the following table:  

Device ID 

Function id 

Start Address 

Model Code 

CRC16 

01 

  03 

02 

55 3C 00 01 

3A 79 

        Response should be in the data, the first byte 01 indicates that the real address of the current device is, 
55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 

00 01 Indicates that the device has a status quantity. 

        (2)Change device address 

        For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 

00 02 E8 14 . 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 66 

00 02 

E8 14 

        After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format 

is parsed as shown in the following table: 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

  06 

00 66 

00 02 

E8 27 

        Response should be in the data, after the modification is successful, the first byte is the new device 

address. After the general device address is changed, it will take effect immediately. At this time, the user 

needs to change the query command of the software at the same time.   

Summary of Contents for SM2130B-H2

Page 1: ...9 24V 1A Dimensions 110mm 85mm 42mm Wiring instructions Any incorrect wiring can cause irreversible damage to the product Please carefully wire the cable as follows in the case of power failure and then connect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wi...

Page 2: ...FA is 250 for the general address When you don t know the address you can use 250 to get the real device address 00 64 is the device model register For the correct query command the device will respond for example the response data is 01 03 02 07 12 3A 79 the format of which is as shown in the following table Device ID Function id Start Address Model Code CRC16 01 03 02 55 3C 00 01 3A 79 Response ...

Page 3: ...queried accordingly Modified 5 Read Correction Value 1 Read Correction Value When there is an error between the data and the reference standard we can reduce the display error by adjusting the correction value The correction difference can be modified to be plus or minus 1000 t hat is the value range is 0 1000 or 64535 65535 For example when the display value is too small we can correct it by addi...

Page 4: ...ng any intellectual property rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes no warranties express or implied regarding the sale and use of this product including the suitability for the specific use of the product the marketability or the infringement liability for any patent copyright or other intellect...

Reviews: