                SM2130B-H2    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page1

 

 

SM2130B-H2 

RS485 interface protection type hydrogen H2 sensor 

User Manual   

 

File Version: V21.3.24

   

        SM2130B-H2 using the standard    RS485 bus MODBUS-RTU protocol,easy access to PLC

DCS and 

other instruments or systems for monitoring hydrogen state quantities.The internal use of high -precision 

sensing core and related devices to ensure high reliability and excellent long-term stability,can be 
customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output 

methods. 

        Technical Parameters 

Technical parameter 

Parameter value 

Brand 

SONBEST 

H2 range 

0~1000ppm 

H2 accuracy 

±

7%FS 

Communication Interface 

RS485 

Default baud rate 

9600 8 n 1 

Power 

DC9~24V 1A 

Dimensions 

110mm×85mm×42mm 

        Wiring instructions 

        Any incorrect wiring can cause irreversible damage to the product. Please carefully wire the cable as 

follows in the case of power failure, and then connect the cable to confirm the correc tness and then use it 

again.   

ID 

Core color 

Identification 

Note 

Red 

V+ 

Power + 

Green 

V- 

Power - 

Yellow 

A+ 

RS485 A+ 

Blue 

B- 

RS485 B- 

                                     

        In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the 

core color is for reference. 

        Communication Protocol 

        The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands 
are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 

9600, 8, n, 1   

        1. Read Data (Function id 0x03) 

        Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the 

command:01 03 00 00 00 01 84 0A . 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

Summary of Contents for SM2130B-H2

Page 1: ...9 24V 1A Dimensions 110mm 85mm 42mm Wiring instructions Any incorrect wiring can cause irreversible damage to the product Please carefully wire the cable as follows in the case of power failure and then connect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wi...

Page 2: ...FA is 250 for the general address When you don t know the address you can use 250 to get the real device address 00 64 is the device model register For the correct query command the device will respond for example the response data is 01 03 02 07 12 3A 79 the format of which is as shown in the following table Device ID Function id Start Address Model Code CRC16 01 03 02 55 3C 00 01 3A 79 Response ...

Page 3: ...queried accordingly Modified 5 Read Correction Value 1 Read Correction Value When there is an error between the data and the reference standard we can reduce the display error by adjusting the correction value The correction difference can be modified to be plus or minus 1000 t hat is the value range is 0 1000 or 64535 65535 For example when the display value is too small we can correct it by addi...

Page 4: ...ng any intellectual property rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes no warranties express or implied regarding the sale and use of this product including the suitability for the specific use of the product the marketability or the infringement liability for any patent copyright or other intellect...

Reviews: