background image

               

                SD8603B    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page3

 

        For the correct query frame, the device will respond with data:01 03 0C 00 79 00 7A 00 7B 00 7C 00 

7D 00 7E 86 BA , the response format is parsed as follows:   

Device 

ID 

Function 

id 

Data 

Length 

data 1 

data 2 

data 3 

data 4 

data 5 

data 6 

 

01 

03   

0C 

00 79 

00 7A 

00 7B 

00 7C 

00 7D 

00 7E 

 

        Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is 

converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. 

Others and so on. 

        2. Data Address Table 

Address 

Start Address 

Description 

Data type 

Value range 

40001 

00 01 

temperature 

read 

0~65535 

40002 

00 02 

humidity 

read 

0~65535 

40003 

00 03 

carbon dioxide 

read 

0~65535 

40004 

00 04 

soil Moisture 

read 

0~65535 

40005 

00 05 

soil temperature 

read 

0~65535 

40006 

00 06 

Radioactivity 

read 

0~65535 

40101 

00 64 

model code 

read/write 

0~65535 

40102 

00 65 

total points 

read/write 

1~20 

40103 

00 66 

Device ID 

read/write 

1~249 

40104 

00 67 

baud rate 

read/write 

0~6 

40105 

00 68 

mode 

read/write 

1~4 

40106 

00 69 

protocol 

read/write 

1~10 

        3 read and modify device address 
        (1) Read or query device address 

        If you don't know the current device address and there is only one device on the bus, you can use the 

command FA 03 00 64 00 02 90 5F Query device address. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

FA 

03 

00 64 

00 02 

90 5F 

        FA is 250 for the general address. When you don't know the address, you can use 250 to get the real 

device address, 00 64 is the device model register. 

        For the correct query command, the device will respond, for example the respon se data is: 01 03 02 

07 12 3A 79, the format of which is as shown in the following table:  

Device ID 

Function id 

Start Address 

Model Code 

CRC16 

01 

  03 

02 

55 3C 00 01 

3A 79 

        Response should be in the data, the first byte 01 indicates that the real address of  the current device is, 

55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 

00 01 Indicates that the device has a status quantity. 

        (2)Change device address 

        For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 

00 02 E8 14 . 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 66 

00 02 

E8 14 

        After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format 

is parsed as shown in the following table: 

Summary of Contents for SD8603B

Page 1: ...he standard RS485 bus MODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring temperature humidity carbon dioxide soil Moisture soil temperature Radioactivity state quantities The internal use of high precision sensing core and related devices to ensure high reliability and excellent long term stability can be customized RS232 RS485 CAN 4 20mA DC0 5V 10V ZIGBEE L...

Page 2: ...H 90 RH Wiring instructions Any incorrect wiring can cause irreversible damage to the product Please carefully wire the cable as follows in the case of power failure and then connect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wire the wires as shown in the...

Page 3: ...read and modify device address 1 Read or query device address If you don t know the current device address and there is only one device on the bus you can use the command FA 03 00 64 00 02 90 5F Query device address Device ID Function id Start Address Data Length CRC16 FA 03 00 64 00 02 90 5F FA is 250 for the general address When you don t know the address you can use 250 to get the real device a...

Page 4: ...the command is 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 Device ID Function id Start Address Target Baud Rate CRC16 01 03 00 66 00 01 64 15 Change the baud rate from 9600 to 38400 changing the code from 3 to 5 The new baud rate will take effect immediately at which point the device will lose its response and the baud rate of the device should be queried accordingly Modified 5 Read Correction ...

Page 5: ...er This document provides all information about the product does not grant any license to intellectual property does not express or imply and prohibits any other means of granting any intellectual prop erty rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes no warranties express or implied regarding the sale...

Reviews: