F-H-A
Baud rate
The following transmission rates in bps (baud) can be selected:
1ˈ200
2ˈ400
4ˈ800
9ˈ600 (default)
19ˈ200
38ˈ400
57ˈ600
115ˈ200
F-H-B
Parity, stop bits
The following combinations of parity and stop bits can be selected:
Option
Description
no par, 1 stop (default)
No parity and 1 stop bit
no par, 2 stop
No parity and 2 stop bits
even par, 1 stop
Even parity and 1 stop bit
odd par, 1 stop
Odd parity and 1 stop bit
F-H-C
Minimum response time
Setting of this parameter avoids interference of communication at the RS-485 interface. For this pur-
pose the response to a command is delayed by the selected time. Additionally, the response is kept
compact.
Unit
ms
Milliseconds
Value range
0…2ˈ000
10 (default)
F-H-D
Transmitter warm-up time
The transmitter warm-up time defines the time before data is sent.
12