Adding a remote control without accessing the motor head (see user guide on page 5)
With a Keygo (Fig. 12a)
With a Telis or similar (Fig. 12b)
CLEARING REMOTE CONTROLS AND ALL SETTINGS
Code
Description
Values
Comments
PA
Maintenance required
indicator
0: no indication
1: 100 cycles
to
99: 9900 cycles
(number of cycles = value x 100 cycles)
Once the motor reaches the programmed number of cycles, the integrated
light flashes each time the door moves to signal that maintenance is required.
To stop the integrated light flashing, either the current value must be confirmed
or modified, or the maintenance indicator must be deactivated.
Pb
Detection of forced entry
0: no detection of forced entry
1: obvious forced entry detected
2: less obvious forced entry detected
Detection of forced entry starts operating 30 seconds after the door is closed.
If forced entry is detected, the siren sounds for 2 minutes. To stop it, press one
of the buttons on the remote control.
If photoelectric cells are installed (P2=2), these must be connected to the
permanent power supply (refer to the installation manual for the siren).
A0
Safety action prior to
opening (safety ADMAP)
0: no effect
1: movement rejected
If value 1 is selected, triggering the safety input will inhibit door opening.
A1
Safety action during closure 1: stop
2: stop + partial re-opening
3: fully reopen
Value 1 is not allowed when using a sensor bar on the safety input.
A2
Obstacle detection action
during closure
2: stop + partial re-opening
3: fully reopen
t0
Total operating mode
automatic timed close
0 to 12 (time delay value = value x 10 s)
2: 20 s
t1
Lighting time delay
0 to 60 (time delay value = value x 10 s)
6: 60 s
t2
Partial operating mode
automatic timed close
0 to 12 (time delay value = value x 10 s)
2: 20 s
(Boldface text = default values)
Programming example:
setting the ”
P7
” closure approach speed
(Fig. 32)
Setting up a long soft stop function zone
“P7” = 2.
Special case: adjusting the position of the door for partial opening (Fig. 33)
Select setting “
P6
” and validate by pressing “
OK
”.
Move the door to the desired partially open position:
. Pressing and holding the “
-
” button will close the door.
. Pressing and holding the “
+
” button will open the door.
. Validate by pressing “
OK
”.
. Exit the menu with
“SET”
.
Forced mode (Fig. 34)
This function is used to move the door to a specific position:
. Pressing and holding the “
-
” button will close the door.
. Pressing and holding the “
+
” button will open the door.
Memorising the remote control for operation in «Partial opening» mode (Fig. 35)
Memorising the remote control for controlling remote lighting (Fig. 36)
Memorising a Telis or similar type remote control (Fig. 37)
SPECIAL OPERATION
Refer to the User’s Manual page 4.