6.5.2 Moco Settings
This menu allows you to adjust the Motor Controllers, assign them to the corresponding zones and to test
them.
You can also
•
enter the runtimes and angles
•
assign the sensor inputs from a 2-unit or 4-unit animeo IB+ Motor Controller to one or more drive
outputs ("software-based jumper")
•
determine "my Position" (individual intermediate position)
•
lock Motor Controllers
6.5.2.1 Test Zones
Here you can check whether all motor controllers (potentially motor controllers with integrated operator but-
ton, such as Smoove UNO IB+) are correctly connected. Please work your way through the commands from
"Step 1" to "Step 3" one after the other. A visual inspection of the entire sun protection system is required
after each step. If the end products/motorized products are not moved to the position where they should be
according to the functional description in the display, have your system re-checked by a specialist.
It is important that you always complete the procedure with step 3, as the local controls (buttons in the room)
will otherwise be locked. You may need to execute this command several times to ensure that all end prod-
ucts/motorized products have ultimately moved to the limit switch position of their drive.
Note:
1. "Down Command" means that the end products/motorized products (roller shutters, Venetian blinds,
etc.) are being lowered or that a window is being opened.
2. "Up Command" means that the end products/motorized products (roller shutters, Venetian blinds, etc.)
are being raised or that a window is being closed.
3. „Up Command“ means that the end products/motorized products( roller shutters, Venetian blinds etc.)
are being raised and manual control is unlocked.
The following errors should be eliminated by a specialist:
1. Several or all drives move in the wrong direction.
Cause:
The up and down connections on the drive of the motor controller have been swapped.
2. The motor controller (for 1, 2 or 4 drives) does not execute any command.
Potential faults:
•
The motor control unit has no mains voltage.
•
The bus is not correctly connected (pay special attention to "com" and "IB+" wires).
If your system is connected correctly, the red LED on the motor controller will light up as soon as a com-
mand is received here. If this is not the case, please have your system checked again by a specialist.
3. Several drives are not being activated (i.e. they do not move to the intended position).
Potential faults:
•
Check the fuses on the motor controller (only for 4-unit device).
•
The thermal protection may have been activated on one drive (e.g. after many long movements). Wait
15 minutes and then repeat the test.