Mounting
SolBatt Home_User Manuel_B.00-EN
9/24
For wall mounting, make sure that the wall is able to carry the weight.
The maximum altitude for installation is 2000 meters above sea level. Derating factors must be
considered for installations at greater altitudes.
The recommended ambient temperature is in the range of >0 °C to +35 °C.
The distance between the top and bottom of the device and any other objects must be a minimum
of 30 cm, preferably 50 cm.
The distance between the left and right side of the device and any other objects must be a
minimum of 20 cm, preferably 30 cm.
The SolBatt Home must be mounted on a non-flammable surface.
Installation in coastal areas is only permitted in sealed rooms. The reason for this is salt spray that
can cause corrosive damage to the housing, both externally and internally.
Attention: The SolBatt Home must never be exposed to ammonia or other aggressive vapours or
gases (stables!). Solutronic Energy provides no guarantees for installations in such areas. The dealer
or installer must pay for any damage in the event of possible subsequent maintenance.
6.2
Wall mounting guide
The SolBatt Home is mounted with the aid of a wall bracket on a suitable wall that can take the weight.
No information can be provided here on suitable fixing materials due to the variety of fixing surfaces
(wall structure).
Use fixing material that you deem to be suitable.
Please note that the device weighs approx. 80 kg!
The person carrying out the mounting is liable for the work.
STEP1
Preparation
S1.1 Required tools
Hammer drill
Φ
12mm drill
(Length 120mm+)
Hand drill
Φ
4mm HEX Socket
(100 mm length)
PH2×100 Cross
screwdriver
Level ruler