28
UM0011_ASW 30-50K-LT-G2_EN_V03_1121
(M4x10), and finally tighten the waterproof connector. (Torque
M4:1.6Nm; M6:5Nm; M8:12Nm; M63:SW65,10Nm)
5.4.3 Additional grounding connection
If additional grounding or equipotential bonding is required
locally, you can connect additional grounding to the inverter. This
prevents touch current if the grounding conductor on the AC
connector fails.
Procedure:
1. Align the terminal lug with protective conductor.
2. Insert the screw through the hole located at the housing and
tighten it firmly (screw driver type: PH2, torque: 2.5Nm).