1-6
*Use only test leads and clips provided by Solmetric for the PVA-1500xx.
PVA-1000S I-V Measurement Unit Specifications
Safety Rating: Measuring Category CATIII 1000V.
Table 3. PVA-1000S electrical and mechanical specifications
Parameter
Specification
Voltage range
0
– 1000 V
Current range
1
0
– 20 A
Voltage accuracy (0 to 55C)
±0.5% ±0.25 V
Current accuracy (0 to 55C)
±0.5% ±0.04 A
Voltage resolution
25 mV
Current resolution
2 mA
Measurement duration
4s (typical)
2
I-V sweep duration
3
0.05 - 2s. Typically 0.2s for PV strings.
Minimum recommended repetition rate:
15s
Number of I-V trace points
100 or 500 (user controlled)
Wireless range (direct to PC, open line of
sight)
100m US only. (Range for Europe pending
evaluation at European mandated
maximum radiated power level).
Operating temperature range
-10 to +65ºC
Storage temperature range
-20 to +65ºC
Operating humidity
<90% RH, non-condensing. Avoid exposing
a cold instrument to warm and humid air as
condensation will result. Store the
instrument in the same conditions in which
it will be used.
Battery charging time
6 hr.
Battery run time
12 hours of continuous operation; more
than 1000 measurement sweeps
Protective features
Over-voltage, over-current, over-
temperature, reverse polarity
PV connector
MC-4