Solidyne WTS-DB Quick Start Manual Download Page 2

 

00-WTS-DB  REV 1  11/2005  

Wiring Cont’d 

 
CAT-5 Wiring: 

Jumper Configuration 

 
The WTS-DB has 3 jumper configurations.  The default jumper 
position is JP2 only.  Other jumper configurations are reserved 
for future use and not applicable at this time. 

CAT-5 Input Assignment: 
 
When using the CAT-5 wiring, the M2 controllers will automati-
cally assign it’s inputs to pre-defined locations: 

Figure 4 

 

M2 

M2V 

Temperature Sensor 

Input 1 (AI1) 

Input 1 (Zone 

Temp) 

 

Setpoint 

Virtual 1 (VI1) 

Virtual 1 (VI1) 

Light Level Sensor 

Virtual 2 (VI2) 

Virtual 2 (VI2) 

Table 1 

Figure 5 

M2-HH Commissioning Tool 

 
The WTS-DB has a small 5 pin connector on the bottom end of 
the device which is used to connect the M2-HH hand held com-
missioning tool.  Please see the 00-M2-HH documentation for 

Installation 

 
The WTS-DB backplate will install easily onto any 2”x4” electrical box 
with the supplied 1” screws.  An electrical box is not necessary for 
proper installation of the WTS-DB.  The 1” screws have a flat head, if 
longer screws are needed, please make sure they have a flat head. 
 
Once the backplate is installed and wiring is completed, install the 
WTS-DB sensor onto the backplate at an angle starting at the bot-
tom of the sensor as shown in figure 6. 
 
After sliding the WTS-DB sensor onto the support bracket of the 

backplate, rotate the sensor towards the wall and secure the WTS-
DB sensor in place by installing the supplied set screw as shown in 
figure 7. 

Figure 6 

Figure 7 

 

Modes of Operation 

 
The WTS-DB has 4 configurable modes of operation.  Each of the 4 
modes displays the zone temperature (either °F or °C) until a button 
is pushed on the unit.  The different modes only change the way the 
setpoint is displayed/used. These different modes of operation are 
listed below. 
 
Mode 1 
 
This mode is the default mode for the WTS-DB.  This gives the user 
an interface to view the room temperature and adjust the setpoint 

numerically.  When the user changes the zone setpoint on the WTS-
DB, the value will be set to Virtual Input #1.  By default, the user 
can set the zone setpoint from 55 to 85. 
 
Mode 2 
 
This mode gives the user an interface to view the room temperature 
numerically, but the setpoint for the zone is displayed via the 7 LED 
level indicator.  This 7 LED level indicator has 3 red LED’s and 3 blue 
LED’s and 1 green LED in between the 3 red and 3 blue LED’s.  
When the user adjusts the zone setpoint the value will be set to 
Virtual Input #1.  By default, the 7 LED level indicator has a range of 
+3 to –3 where 0 will be set to Virtual Input #1 when the middle 
green LED is set.  See Figure 8 for details of the LED level indicator. 
 
Mode 3 

 
This mode eliminates the user zone setpoint all together.  It does 
however allow the user to view the current zone temp and send a 
system override. 
 
Mode 4 
 
This mode is the same as Mode 3, but the LED level indicator is used 
to display how warm or cool the room is based on Virtual Input #1 
which would be set by a device other than the WTS-DB (ie. ICMS 
graphic).  With the highest red LED lit, the room is 3 or more de-
grees warmer than Virtual Input #1.  With the lowest Blue LED lit, 
the room is 3 degrees cooler than Virtual Input #1 

Reviews: