3. INSTALLATION
The equipment must be installed in a heated room in the home (>10ºC) if this
is not possible, the condensate outlet must be thermally isolated
In areas that regularly have negative temperatures (<-2ºC)
a pre-heating battery must be installed. Operating temperature (<-2ºC, 45ºC)
Ducts must be thermally insulated and correctly installed.
ORKA has been designed to be installed indoors.
Uninsulated
duct
Insulated
duct
Insulated
duct
Spigot arrangement Ø 150 mm
Spigots that are not used must be plugged with the supplied accessory.