PE Connection and Leakage Current
• The inverter incorporates a certified internal Residual Current Device (RCD)
in order to protect against possible electrocution and fire hazard in case of a
malfunction in the cables or the inverter. There are two trip thresholds for the RCD
as required for certification (IEC 62109-2:2011). The default value for eletrocution
protection is 30mA, and for slow rising current is 300mA.
• If an external RCD is required by local regulations, check which type of RCD
is required for relevant eletric code. It recommends using a type-A RCD. The
recommended RCD values is 100mA or 300mA unless a lower value is required
by the specific local electric codes. When required by local regulations, the use of
an RCD type B is permitted.
The device is intended to connect to a PV generator with a capacitance limit of
approx 700nf.
High leakage current!
Earth connection essential before connecting supply.
WARNING
!
• Incorrect grounding can cause physical injury, death or equipment malfunction
and increase electromagnetic.
• Make sure that grounding conductor is adequately sized as required by safety
regulations.
• Do not connect the ground terminals of the unit in series in case of a multiple
installation. This product can cause current with a d.c component, Where a residual
current operated protective (RCD) or monitoring (RCM) device is used for protection
in case of direct or indirect contact, only one RCD or RCM of type B is allowed
on the supply side of this product.
For United Kingdom
• The installation that connects the equipment to the supply terminals shall
comply with the requirements of BS 7671.
• Electrical installation of PV system shall comply with requirements of BS 7671
and IEC 60364-7-712.
• No protection settings can be altered.
• Installer shall ensure that equipment is so installed and operated to maintain
at all times compliance with the requirements of ESQCR22(1)(a).
For Australia and New Zealand
• Electrical installation and maintenance shall be conducted by licensed
electrician and shall comply with Australia National Wiring Rules.
09
08
2.3 Explanation of Symbols
This section gives an explanation of all the symbols shown on the inverter and
on the type label.
Symbols on the Inverter
Symbol
Explanation
The inverter is working normally, when the blue light is on.
An error has occurred, when the red light is on.
Symbols on the Type Label
Symbol
Explanation
CE mark.
The inverter complies with the requirements of the applicable
CE guildlines.
RCM remark.
SAA certification.
Beware of hot surface.
The inverter can become hot during operation. Avoid contact
during operation.
Danger of high voltages.
Danger to life due to high voltages in the inverter!
Danger.
Risk of electric shock!
Observe enclosed documentation.
The inverter can not be disposed together with the household waste.
Disposal information can be found in the enclosed documentation.
Do not operate this inverter until it is isolated from mains
and on-site PV generation suppliers.
Danger to life due to high voltage.
There is residual voltage in the inverter which needs 5 min to
discharge.
• Wait 5 min before you open the upper lid or the DC lid.
Safety
Safety
•
•