1. Shut down the T-BAT system (Please refer to
Section 5.4 Shutting Down
T-BAT System
of User Manual on page 30);
2. Remove the lock cover
a. Pull at back end of the lock cover with nger or an instrument;
b. Remove the lock cover and keep it for next time.
Forbid to plug/unplug power cables when the T-BAT system is not turned off,
otherwise there will be an arc discharge that hurt human body!
+
-
+
-
Lock Cover
3. Push the plastic button on each end of the power cable in the direction
of the arrow;
4. Unplug the power cable.
Notes for Unplugging Power Cables
Caution!
4. Installation
4. Installation
20
21
For 2~4 battery modules:
The power cable between battery modules (A1) is different from the one that
between BMS and battery module (C). The other end of the power cable is black,
and this color is connected to YPLG (
Ⅴ
’), which is on the right side of the battery
module.
1. Connect YPLUG (
Ⅴ
’)on the right side of battery module to XPLUG (
Ⅰ
’) on the
left side of the second battery module. The rest battery modules are connected
in the same way. The following figure shows that four battery modules are
connected.
YPLUG
YPLUG
XPLUG
XPLUG
Capacity
Note!
Make sure that GND has been finished before the cable connection!
EARTHBAR