21
TROUBLESHOOTING
Normal Operation Troubleshooting
Should any of the following scenarios occur, please check the
following:
Concern:
Powervent does not start.
Cause:
power vent control is turned off; power vent control
does not have power. “GV60 AUX” harness is not plugged into
the Maxitrol GV60 AUX port.
Check:
1.
Check that “Power LED” is illuminated, if not, turn on
the power vent control.
2.
Connect power to Power vent control.
3.
Check that “GV60 AUX” harness is plugged securely
into the Maxitrol GV60 AUX port.
Concern:
Powervent does not start, “Operation Status LED” is
red.
Cause:
Pressure switch is closed while power vent is off.
Check:
1.
Actuate pressure switch manually (suck on pressure
line), try again. “Pressure LED” should illuminate as
the switch is actuated.
2.
Replace pressure switch.
Concern:
Normal Operation begins as described (left) but
“Operation status LED” turns red after the pilot lights but before
the main burner ignites.
Cause:
Power vent control did not get signal pressure switch
has closed.
Check:
1.
Is the pressure switch plugged in?
2.
Actuate pressure switch manually (suck on pressure
line), does “pressure” LED light up? If not, replace
pressure switch.
3.
Has pressure tube been installed on wrong port on
pressure switch? (Should be connected to light colored
port).
4.
Is the fireplace fully assembled, glass installed on the
fireplace?
5.
Does the fireplace calibrate successfully?
6.
Is the power vent blower running as expected? (easiest
way to check is to press reset button on power vent
board, the 60 second purge cycle should begin, the
“Operation status LED” should be blue, the power vent
blower should be running.
If this troubleshooting guide does not resolve your concern, please
contact SÓLAS at:
Phone:
(603) 298-5169
Email:
PRESSURE LED
OPERATION STATUS LED
POWER LED
ON/OFF SWITCH
OPERATION STATUS LED
PRESSURE LED
RESET BUTTON
INSTALL PRESSURE TUBE ON THE GREY PORT