Solas-Nua FS-16N RV Installation & Operation Manual Download Page 6

 

INSTALLATION REQUIREMENTS 

The gas fireplace is shipped with a plugged 3/8” Stainless Steel Flex Connector exiting the bottom rear of 
the stove.  The gas supply piping should have a separate gas shutoff valve and a 1/8” NPT plugged tapping 
upstream of the valve. The stove and its main control valve must be disconnected from the gas supply pip-
ing system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). The 
stove must be isolated from the gas supply piping system by closing the main control  valve during any 
pressure testing of the gas supply system at test pressures equal to or less than 1/2 psi (3.5kPa) After the gas 
supply has been connected, use a commercial gas leak detector or apply a soapy water solution to all fit-
tings to check for gas leaks. Never use a flame to test for leaks.  

REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS 

This product must be installed by a licensed plumber or gas fitter when installed within the Com-
monwealth of Massachusetts.  If this appliance is installed in a dwelling, building or structure used in 
whole or in part for residential purposes and the installation includes a horizontal vent termination 
that is less than seven (7) feet above the finished grade in the area of the venting, including but not 
limited to decks and porches, a hard-wired carbon monoxide detector with an alarm and battery 
back-up must be installed on the floor level of the dwelling, building or structure where the appli-
ance is to be installed. 
Additionally, a hard-wired or battery operated carbon monoxide detector with an alarm must be in-
stalled on each additional level of the dwelling, building or structure served by the appliance. It shall 
be the responsibility of the property owner to secure the services of qualified licensed professionals 
for the installation of hard-wired carbon monoxide detectors. 

In the event that the horizontally vented appliance is installed in a crawl space or attic, the hard-
wired carbon monoxide detector with alarm and battery back-up may be installed on the next adja-
cent floor level. 
In the event that this requirement cannot be met at the time of completion of the installation of the 
appliance, the owner shall have a period of thirty (30) days to comply with the requirement. How-
ever, during said thirty (30) day period, a battery operated carbon monoxide detector with alarm 
must be installed. 
Each carbon monoxide detector as required in accordance with the above provisions must comply 
with NFPA 720 and be ANSI/UL 2034 and IAS certified. 
In addition when the vent termination is less than seven (7) feet above finished grade a metal or plas-
tic identification plate must be permanently mounted to the exterior of the building at a minimum 
height of eight (8) feet above grade directly in line with the exhaust vent terminal.  The sign shall 
read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.  KEEP 
CLEAR OF ALL OBSTRUCTIONS”. 
A COPY OF THESE INSTRUCTIONS PLUS ALL VENTING INSTRUCTIONS WHICH IN-
CLUDE PARTS LISTS, AND/OR ALL VENTING DESIGN INSTRUCTIONS MUST REMAIN 
WITH THE STOVE AT THE COMPLETION OF THE INSTALLATION. 
ATTENTION INSTALLERS:  Mark below which venting system was used in the installation.  These 
instructions must remain with the Installation & Operation Manual.  

 
 Simpson DuraVent GS/PRO

®

              Selkirk Direct-Temp

®

         

Security Secure Vent™ 

      

           

 

 

AmeriVent Direct™

 

Metal Fab Direct Vent

 

ICC Direct Vent

 

Summary of Contents for FS-16N RV

Page 1: ...lowed exactly a fire or explosion may result causing property dam age personal injury or loss of life WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch d...

Page 2: ...NSTALLATION RECORD FORM 38 WARRANTY INFORMATION 39 TABLE OF CONTENTS WE STRONGLY SUGGEST THAT YOU READ THIS MANUAL THOROUGHLY BEFORE BE GININNG THE INSTALLATION OF THE SOLAS NUA FREESTANDING DIRECT VE...

Page 3: ...of the appliance A commercially available hearth pad meets this requirement The appliance area must be kept clear and free from combustible materials gasoline and other flammable vapors and liquids Th...

Page 4: ...r use with the fuel type indicated on the rating plate This appliance has been certified by OMNI Test Laboratories Inc to ANSI Z21 88a 2007 CSA 2 33a 2007 Vented Gas Fireplace Heaters and CAN CGA 2 17...

Page 5: ...ruction are listed below In addition access to the gas supply must be considered The location of the stove will also affect the venting requirements and you must be certain the location will allow com...

Page 6: ...d on each additional level of the dwelling building or structure served by the appliance It shall be the responsibility of the property owner to secure the services of qualified licensed professionals...

Page 7: ...installation will include at least one 90 elbow Up to three additional 90 elbows or equivalent 45 elbows may also be used The total venting may not exceed 20 feet of vertical rise and or 10 feet hori...

Page 8: ...r stove will not be venting directly though an outside wall to a horizontal termination or if more than 30 of horizontal vent run is required some vertical vent rise will be required for the fireplace...

Page 9: ...B NU B NU B NU 11 10 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU 10 9 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU 9 8 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU...

Page 10: ...B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 10 9 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 9 8 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 8 7 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 7 6 B 4 B 4...

Page 11: ...A VERTI CAL RISE AND HORIZONTAL RUN SNORKEL CAPS HAVE BUILT IN VERTICAL RISE THAT MUST BE COUNTED D TOTAL NUMBER OF 90 ELBOWS _______ NOTE SNORKELS COUNT AS 2 90 ELBOWS E TOTAL NUMBER OF 45 ELBOWS __...

Page 12: ...zontal Run Exhaust Restrictor Required B Air Restrictor Tabs Open 3 A Fuel LP Gas B Total Vertical Vent Rise 2 feet C Total Horizontal Vent Run Actual 10 feet D 90 Elbows Needed 2 E 45 Elbows Needed 0...

Page 13: ...13 VENT TERMINAL CLEARANCES Venting terminals shall not be recessed into a wall or siding...

Page 14: ...items 1 Installation and operation Manual 2 A C Adapter 3 Vent Restrictor Kit 4 Glass Media burner 5 Remote Control 6 Battery Pack 7 Levelling bolts 4 8 Blow Off Relief Door The stove has been bolted...

Page 15: ...page 7 to make that determination If your installation does require an air restrictor or exhaust restrictor or both these must be installed be fore you connect your vent system to the stove Again refe...

Page 16: ...ove body 6 Place the vent starter pipe gasket on the back of the stove aligning the holes in the gasket with the pilot holes on the rear of the fireplace 7 Align the inner pipe of the vent starter pip...

Page 17: ...lly clip one corner of the poly bag to form a pouring spout The opening should be large enough to allow the glass media to flow but not so large that you can t control the flow 3 You will notice that...

Page 18: ...f door enough to allow the rear line up tab to engage the rear retainer slot Refer to the sec ond illustration below 5 Rotate the front edge of each relief door so they line up over front retainers 6...

Page 19: ...Replace the battery pack on the bracket and secure with the hook and eye strap 6 Reconnect the battery connector to the Electronic Module Note An optional A C adapter is also supplied with the unit a...

Page 20: ...tom front of the fire box Take care to center the frame from left to right 3 Once the bottom edge is in place move your fingers out of the way and press the top of the frame against the firebox while...

Page 21: ...system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5kPa 6 The fireplace must be isolated from the gas supply piping system by closing the gas shut off valve dur...

Page 22: ...the pilot Do not try to light the pilot by hand 3 If using the Remote Handset push the button until you hear an audible signal to insure the appliance is off 4 Wait five 5 minutes to clear out any ga...

Page 23: ...burner has been in operation for a few minutes the flames should look like those in the illustration below Note The flame height will vary depending on the firing rate setting but flames should be eve...

Page 24: ...te that the system has accepted the order and the flame will light on the High setting To decrease the flame level press the DOWN button A beep and a flash of the LED indicate that the sys tem has acc...

Page 25: ...me C Signal strength D Selected working mode E Selected setting F Current flame status G Current fan status Not Applicable on this appliance H Current room temperature I Child lock status J Button lab...

Page 26: ...ible that the remote is locked in the OFF screen to unlock it just press the button below Unlock and then OK 2 3 Switching on Once the remote is unlocked press ON left button and OK middle button A be...

Page 27: ...27 COPRECI R emotion CONTROL SYSTEM...

Page 28: ...et in the configuration menu This specified the maximum permitted room temperature This temperature can never be set higher than 104 F 40 C It is recommended you set to 95 F 35 C Auto Thermostatic Mod...

Page 29: ...ppliance will heat until this temperature is reached Comfort Temp The comfort temperature is set as the desired temperature and the appliance will heat until this temperature is reached Finally to lau...

Page 30: ...ou get to main screen PS If pairing has been attempted previously and has not been achieved try the follow ing Press and hold the OFF button for 40 seconds Set the channel on channel A Select On in th...

Page 31: ...possible range of values is 77 104 F 25 40 C Suggested setting is 95 F 35 C Channel There are three different channels available A Band C These different channels make it possible to have more than o...

Page 32: ...32 TROUBLESHOOTING...

Page 33: ...e in the frame so it is very important to support both the glass and the frame when handling Place your thumbs on the outside of the glass frame and wrap your fingers around the frame and onto the gla...

Page 34: ...Burner and Firebox During the annual inspection and maintenance appointment the service person should clean the burner and firebox To gain access to the firebox and burner follow the instructions begi...

Page 35: ...Gas Connections Other __________________________ MAINTENANCE LOG Date of Service ____________________ Serviced By ______________________ Service Performed Inspect Venting Clean Burner Firebox Clean C...

Page 36: ...36...

Page 37: ...ls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing A B C D E F G H Caution Label all wires prior to disconnection when servicing the controls Wiring er...

Page 38: ...ow that describes the details of the installation Having this writ ten record of installation information available will greatly expedite trouble shooting should any problem arise with your stove The...

Page 39: ...39 4 Technology Drive Suite 5 West Lebanon NH 03784 Telephone 603 298 5169 Fax 603 298 9246 Sales hearthinnovations com...

Page 40: ...40 V1 01 2013 Manufactured by Progressive Manufacturing Inc 4 Technology Drive Suite 5 West Lebanon NH 03784 USA www hearthinnovations com...

Reviews: