9.4.3 Modbus Errors
When using an external device to read probes using Modbus communications, the relevant reading status parameter should also be
read to confirm the validity of the reading.
ReadingStatus Value
Displayed Value
Meaning
0
OK
Reading Valid
18
URangeA
Under Range for Channel / Module
19
ORangeA
Over Range for Channel / Module
246
246
Incompatible probe connected
247
247
No probe connected
With the ASCII based serial communications, the 'Limit' character indicates the probe's error status.
503110 - Orbit ACS Manual
Issue 9
32 of 63