SolarPro VC21 Installation Manual Download Page 8

7

VC21  

INSTALLATION GUIDE

Real Time Energy Metering

VC21 User Manual

UPDATED: 10.9.12

Static IP Address Setup:

•  STEP 1

LCD display, press and hold the menu (top) button on the server for several 
seconds and the message should appear. To change the IP address to the static 
address assigned by the network administrator, do the following:

A. Press the menu (top) button once to get the TCP/IP configuration menu

[Main Menu]
TCP/IP Config

B. Press the select (bottom) button twice to get the IP config menu:

[TCP/IP Config]
IP Address

C. Press the select button again to see the IP address menu:

[IP Address]
192.168.40.50

D. At this point, the cursor on the display will be blinking on the first number in 
the IP address on the second line.

E. To change the number, press the menu (top) button and the display will cycle 
through the digits 0-9 as well as “.”. Once the correct digit is displayed, press the 
select (lower) button to advance to the next digit and repeat the process until all 
the digits are correct.

F. Once the IP address on the AcquiSuite matches the assigned IP address, press 
the select (bottom) button once more to return to the main TCP/IP menu.

•  STEP 2

Set the netmask, gateway, and DNS server(s) addresses using the same technique 
as shown above. The only change is that after Step B, press the menu (top) 
button multiple times to see the netmask, gateway, and DNS setup menu, then 
push the select button to set the option.

NOTE: If DHCP configuration is selected, the IP, netmask, gateway, and dns 
server addresses will be obtained automatically. Simply select the “Enable DHCP” 
from the first TCP/IP configuration menu.

Summary of Contents for VC21

Page 1: ...tting Started 1 SORAPRO Hardware 2 Installation Overview 4 Network Commissioning 6 Installation Checklist 8 Accessories 9 Troubleshooting 10 Technical Data 13 Support 14 Warranty 15 Appendix A 16 TABL...

Page 2: ...visualize where all the equipment will need to be installed and do a soft installation before mounting any equipment If you do not understand the instructions in full please contact SORAPRO Support at...

Page 3: ...RO installation Manufacturer of each component will vary depending on the equipment specified for the solar installation 1 3 Pole 20A Circuit Breaker 2 14 AWG 600V wire 3 Conduit or larger with Liquid...

Page 4: ...Option the unit will contain two revenue grade metering devices One device will be labeled PV and the second device will be labeled LOAD To ensure proper data collection make sure to connect the corr...

Page 5: ...to ensure proper metering the CT s must be installed in the same panel as the breaker you are installing in this step 4 Install the CT s on the solar output wires 5 Install a watertight 3 4 or larger...

Page 6: ...aker panel to the SORAPRO device 7 Using the conduit from step 5 run the CT wires from the breaker panel to the SORAPRO device The SORAPRO device will come standard with 10 leads on the CT s Loop any...

Page 7: ...ess which is assigned by a network administrator and configured into the AcquiSuite Dynamic Host Configuration Protocol DHCP address this process assigns an IP address dynamically to the AcquiSuite wh...

Page 8: ...ress on the second line E To change the number press the menu top button and the display will cycle through the digits 0 9 as well as Once the correct digit is displayed press the select lower button...

Page 9: ...they are facing the correct direction of current flow 2 The AcquiSuite is displaying kW readings on the LCD screen 3 The readings on the AcquiSuite make sense under current conditions 4 All accessori...

Page 10: ...easurements 2 Clamp on Amp meter to verify current in line if possible 3 Basic electrician tools PROBLEM SOLUTION The Alive light does not come on or LCD display it not lit Verify connection on the te...

Page 11: ...ie WattsOn 1100 5A or by the yellow sticker on the face of the unit as below Before commencing other troubleshooting steps ensure that the WattsOn is receiving a proper power supply Power to the Watt...

Page 12: ...factory Double Flash pause Double Flash Firmware update mode check DIP Address switch must not be 0 Potential firmware problem To test for WattsOn functionality it is best to connect power and discon...

Page 13: ...100 to 240 VAC Voltage Range 88 to 264 VAC Current 1 8A max Frequency 60 Hz OUTPUTS Wh Qh solid state relay RS485 Modbus RTU Start Time 1000 ms max Rise Time 30 ms max DEVISE Power Supply 24 VDC Accur...

Page 14: ...equipment and or software it may describe including any implied warranties of utility merchantability or fitness for any purpose All such warranties are expressly disclaimed Neither Future Solutions T...

Page 15: ...at no charge for materials or labor costs Repair at Future Solutions Technologies Exchange for an equivalent Replacement Device In the event of receipt of a Replacement Device the warranty will contin...

Reviews: