![Solaronics SSTG Installation, Operation & Maintenance Instructions Manual Download Page 12](http://html1.mh-extra.com/html/solaronics/sstg/sstg_installation-operation-and-maintenance-instructions-manual_1314011012.webp)
12
WIRING BY
PURCHASER
GREEN (GROUND)
WHITE (NEUTRAL)
FUSED
DISCONNECT
THERMOSTAT
DUAL SYSTEM ONLY
BLACK
(LINE)
TO
BURNER
TO
BURNER
120-1-60
120-1-60 (3 WIRE SERVICE)
(NEUTRAL)
WHITE
TO BURNER
TRANSFORMER/RELAY
(MOUNTED TO 4x4
JUNCTION BOX
PROVIDED BY OTHERS)
FUSED DISCONNECT
(BY OTHERS)
WIRE NUT SYMBOL
WIRING BY OTHERS
GREEN GROUND
SCREW IN 4X4
JUNCTION BOX
WIRE NUT
(BY OTHERS)
NEUTRAL
(HOT)
BLACK
(GROUND)
GREEN
BLACK
BLACK
WHITE
RED
BROWN
HOT
GROUND
R
C
W
Y
G
24 VOLT
THERMOSTAT
BURNER 1
BURNER 2
BURNER 6
BURNER 7
T'STAT
FUSED
120V.
1PH.
HOT
NEUTRAL
GROUND
NOTE: SEE TABLE FOR MAXIMUM NUMBER OF
HEATERS ON A THERMOSTAT
W
Y
R
G
C
TRANSFORMER/RELAY
CAUTION: NO MORE THAN THREE
HEATERS IN A SERIES
NOTE: BROWN WIRE IS NOT USED BUT MAY BE ELECTRICALLY HOT.
PROTECT PERSONNEL AND THE CIRCUIT BY SCREWING ON A WIRE NUT
BROWN
WIRE NUT
BY OTHERS
WIRING BY
OTHERS
GREEN
BLACK
WHITE
GROUND
NEUTRAL
WHITE
BLACK
BLACK
RED
FUSED
DISCONNECT
(BY OTHERS)
GREEN GROUND SCREW
IN 4X4 JUNCTION BOX
BLACK
BLACK
HOT
BURNER 1
BURNER 3
LO-VOLT
T-STAT
ELECTRICAL SUPPLY AND THERMOSTATIC CONTROL
ELECTRICAL SUPPLY
120 VAC THERMOSTATIC CONTROL
HEATERS IN SERIES WITH A 120 VAC THERMOSTAT
•
Voltage: 120 VAC – 1 phase – 60 Hz.
•
Maximum Amps: 3.0 (1.33 actual full load
amps).
•
Flame safety: Electronic.
•
Ignition: Direct Spark.
•
Wiring must conform to the latest edition of the
National Electric Code (ANSI/NFPA 70) or
local code legally authorized.
•
Have a qualified electrician check that the
electrical supply circuit and wall receptacle are
properly grounded and that the electrical
supply polarity is correct. The heater control is
polarity sensitive and will not operate properly
if the electrical supply is not wired correctly.
•
Electrical power takeoff must be connected to
a separately fused circuit with a disconnect,
and must be properly polarized and grounded
to the heaters power cord.
•
Do not run wiring over the heaters or in direct
view of radiant heat.
•
If any of the wiring supplied must be replaced
use type 16 AWG (1.0mm
2
), or equivalent with
2/64” (.08cm) insulation and a minimum
insulation temperature of 302°F (150°C).
GENERAL INSTALLATION NOTES
24 VAC THERMOSTAT AND TRANSFORMER (MAX. 3 HEATERS)
•
Locate the thermostat as specified in the
heating plan.
•
If it is not in the heating plan, follow the
instructions provided with the thermostat.
•
If instructions are not provided with the
thermostat, locate it four to five feet above the
floor where it will not be directly affected by the
heat from the heater, outside drafts, or the
sun.
•
A location that best represents the average
temperature of the room is the most desirable.
•
If two heaters are installed on a common
exhaust vent they must be controlled by the
same thermostat.
CAUTION – 24VAC THERMOSTAT
DO NOT try to connect more than three burners to
a 24 VAC thermostat. The transformer relay is
rated to operate only three heaters safely. Failure
to do so may cause serious bodily harm or property
damage.
ACCESSORY THERMOSTATS
HEATERS IN SERIES WITH A 24 VAC THERMOSTAT
Thermostat
Volts
AC
Amps
Maximum
Number of
Heaters
132026-4
120
22.0
7
132486
120
16.0
5
132700
24
.15-1.0
3*
* When installing these heaters to any thermostat,
the installer should allow for 3 amps per heater as
the blower tends to use more electricity than its
rating during its start-up period. This is why all of
the 24 VAC thermostats must be connected to a
120 VAC transformer relay, which will safely
support only three heaters.
Note: The brown wire is not used, but may be electrically hot. Protect
personnel and the circuit by screwing on a wire nut.