![SOLARFOCUS PelletElegance 10 Manual Download Page 27](http://html1.mh-extra.com/html/solarfocus/pelletelegance-10/pelletelegance-10_manual_1313812027.webp)
5 Installation
6.5 Extension pack for heating circuit 2
Requirement for this extension
þ
The extension for heating circuit 1 (Art.
67261, 67271) must be installed
Schematic: Buffer ch integrated HC1 +
HC2
Overview
Abb. 2-37_006c
1 Buffer return
1a Return booster pump Wilo Yonos PARA RS
15/7.5 RKC
1b Return mixer (3-way mixing valve with ser-
vomotor)
2 Buffer flow
3 Heating circuit 1 - return
4 Heating circuit 1 - flow
4a Heating circuit 1 - Pump Wilo Yonos PARA RS
15/6 RKA
4b Heating circuit 1 - mixing valve (3-way mixing
valve with servomotor)
5 Heating circuit 2 - return
6 Heating circuit 2 - flow
6a Heating circuit 2 - Pump Wilo Yonos PARA RS
15/6 RKA
6b Heating circuit 2 - mixing valve (3-way mixing
valve with servomotor)
6c Flow temperature sensor
Installation steps
►
Remove the closing plugs at
HC1a
and
HC1b
.
►
Install the preassembled pump group
Heating cir-
cuit 2 - group
, connect
HC2a
to
HC1a
and
HC2b
to
HC1b
.
Abb. 2-38_018aAB
►
Bolt the (longer) flow pipe
Heating circuit 2 - flow
6
to the pump housing.
►
Bolt the (shorter) return pipe
Heating circuit 2 -
return
5
to the existing pipe.
►
Fix the temperature sensor
6c
to the flow pipe.
Abb. 2-39_048AB
Installation manual
pelletelegance
27