When installing inverters one above the other, leave at least 8" (20 cm)
between the top of an inverter and the bottom of the Safety Switch.
When installing inverters side by side, follow these clearance
specifications:
Location
Indoor
Installation
Outdoor Installation
Locations where the
annual average high
temperature
(1)
is below
25˚C / 77˚F
20 cm / 8"
between
inverters
5 cm / 2" between inverters (if
inverters are also installed one
above the other, maintain the
indoor installation clearance)
Locations where the
annual average high
temperature
1
is above
25˚C / 77˚F
40 cm / 16"
between
inverters
(1)
Annual average high temperature – the average of the 12 monthly average highs, for
example:
Chapter 3: Installing the Inverter
37
Refer to
to find the value in your location.
Three
Phase
System
Installation
Guide
MAN-01-00527-1.
2