52
L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40,
L15US-IB60 L15US-IB00, L20US-IB60, L20US-IB00 UPS
Model
L10US
L15US
L20US
Frequency tolerance
40-70Hz
Voltage window (At
100%/50% load)
-20%, +25% (166-260Vac or 176-275Vac), Full load
-40%, +25% (125-260Vac or 132-275Vac) , <50% Load
Back feed contact point
Dry contact: 125Vac/0.5A
Power Walk IN(S) for parallel
system
0-200
Dual feed
Standard with busbar configuration as single feed
Input rate current(A)
30/29A
45/43A
60/57A
Input max. current(A)
37/35A
56/53A
75/71A
Battery
Battery types
VRLA
Build-in battery
20/40/60pcs 9Ah
40/60pcs 9Ah
60pcs 9Ah
±
120Vdc
Battery block flexibility
Optional Voltage:
±
96/108/120/132/144/156Vdc (16-20pcs
optional)
192Vdc
~
312Vdc (16~26pcs, 20 pcs define, 20~ 26pcs no
power derating; 18pcs output power factor 0.9;16pcs output
power factor 0.8;)
Charge capacity
13A Max.
Battery temperature
compensation (standard /
optional)
40
℃
/104
°
F
>
T
>
25
℃
/
82.4
°
F , -7~0mV/
℃
,
default
:
no
compensation
Battery test
Manual and automatic programmable by time or voltage
Comm battery
Support
Output
Overload
Online
mode
110% 60mins, 125% 10mins, 150% 1mins